Variable function, Variable digital, Variable analog – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 113
Watlow EZ-ZONE
®
RML Module
•
110
•
Chapter 6 Features
Variable Function
This function simply passes the stored value to its
output.
An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal
Data, Ambient Error, RTD Error, Fail, Math Error,
Not Sourced, Stale
A variable function block is used to store a user sup-
plied value and provide a source input to another
function block with that value. As an example, you
could use a variable function value as one input to
a compare function. The other input to the compare
function would determine the output value based on
the user's supplied value.
Variable
Overview
Instances - 8 per RMC
Data
Type
Digital
Value
Analog
Value
Units
[tyPE]
Data Type : Analog, Digital
[`Dig]
Digital Value : On, Off
[AnLg]
Analog Value : -1,999.000 to 9,999.000
[`uAr]
Variable Menu
[`SEt]
Setup Page
Output Value
Error
[Unit]
Units : None, Absolute Temperature,
Relative Temperature, Power, Process
Relative Humidity
[``ou]
Output Value : -1,999.000 to
9,999.000 or On or Off
Variable
Digital
Data
Type
Digital
Value
Analog
Value
Units
Output Value
Error
Variable
Analog
Data
Type
Digital
Value
Analog
Value
Units
Output Value
Error