Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 75

background image

Watlow EZ-ZONE

®

RML Module

72

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[M;hL]
[M.hL]

Communications

Modbus Word Order

Select the word order of

the two 16-bit words in the

floating-point values.

[hiLo]

Word High Low

(1330)

[Lohi]

Word Low High

(1331)

Low High 3498

0x96 (150)

1

5

- - - -

17043

uint
RWE

[`C_F]
[ C_F]

Communications

Comm Units

Select which scale to use for

temperature over comms.

°F (30)
°C (15)

°F

3500

0x96 (150)

1

6

- - - -

17050

uint
RWE

[`nU;S]
[ nV.S]

Communications (1)

Non-volatile Save

If set to Yes all values writ-

ten to the control will be

saved in EEPROM.

Note:

Any value that is changed

from the RUI or over a

communications port will

initiate a write to the EE-

PROM. Life of EEPROM

is approximately one mil-

lion writes.

[`yes]

Yes (106)

[``no]

No (59)

Yes

3504

0x96 (150)

1

8

198

17051

uint
RWE

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set