Counter function, Custom function, Diagnostic function – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 95: Diagnostics overview instances - 1 per rml, Watlow ez-zone, Rml module, Chapter 6 features

background image

Watlow EZ-ZONE

®

RML Module

92

Chapter 6 Features

Counter Function

Function counts up or down from Load Value and produces

Output Value = On when Count = Target Value.

Note:

Count value clears on power loss.

Load Value restored on power up.

Counter Operation:
Whenever a prescribed clock transition occurs with-

out an error on source B the count will be equal to

the Load Value.
If Function is an Up Counter:
Whenever a prescribed clock transition occurs with-

out an error on Source A the count will increment by

+1. If the count is equal to 9,999 when the transition

occurs count will be 1 after transition.
If Function is a Down Counter:
Whenever a prescribed clock transition occurs with-

out an error on Source A the count will decrement by

-1. If the count is equal to 0 when the transition oc-

curs the count will be 9,999 after transition.

An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal Data,

Ambient Error, RTD Error, Fail, Math Error, Not Sourced,
Stale

[`S2;A]

Source Zone A : 0 to 16

[`S2;b]

Source Zone B : 0 to 16

[`Si;A]

Source Instance A : 1 to 250

[`Si;b]

Source Instance B : 1 to 250

[`Su;A]

Source Value A : Off, On

[`Su;b]

Source Value B : Off, On

[``o;u]

Output Value : Off, On

[trgt]

Target Value : 0 to 9,999

[`LAt]

Latching : No, Yes

[`Cnt]

Count : 0 to 9,999

[SAS;b]

Source Active State B (Active State Load) : High, Low

[LoAd]

Load Value : 0 to 9,999

[``Fn]

Function : Up, Down

Output Value

Error

Source Value A

Source Value B

Counter

Overview

Instances - 16 per RML

Function

Source

Active State

A

Source

Active State B

Source Function A

Source Instance A

Source Zone A

Source Error A

Source Function B

Source Instance B

Source Zone B

Source Error B

Load

Value

Target

Value

Latc

hing

Count

[`Ctr]

Counter Menu

[`SEt]

Operation Page

[`Ctr]

Counter Menu

[`SEt]

Setup Page

[SFn;A]

Source Function A : None, Alarm, Compare, Counter, Digital I/O, Profile

Event Out A to H, Function Key, Logic, Timer, Variable

[SFn;A]

Source Function A : None, Alarm, Compare, Counter, Digital I/O, Profile

Event Out A to H, Function Key, Logic, Timer, Variable

[sas;a]

Source Active State A (Active State Clock) : High (rising), Low (falling),

Both (rising & falling)

Custom Function

Custom

Overview

Instances - 20 per RML

[`iid]

Instance ID : 1 to 24

Instance ID

Parameter

[CUSt]

Custom Menu

[FAct]

Factory Page

[`par]

Parameter : None, Process, Calibration

Offset, Display Units, User Settings Restore,

Alarm Low Set Point, Alarm High Set Point,

Alarm Hysteresis, Set Point, Active Process

Value, Active Set Point, Open-Loop Set Point,

Autotune, Control Mode, Heat Power, Cool

Power, Time Integral, Time Derivative, Dead

band, Heat Proportional Band, Heat

Hysteresis, Cool Proportional Band, Cool

Hysteresis, Ramp Rate, TRU-TUNE+ Enable,

Idle Set Point, Custom, Profile Start, Profile

Action Request, Guaranteed Soak Deviation

Value, Current, Limit Low Set Point, Limit

High Set Point, Limit Hysteresis, Limit Status

Diagnostic Function

Diagnostics

Overview

Instances - 1 per RML

[`rEu]

Software Revision: 1.00, ...

[S;bLd]

Software Build Number : 0, 1, 2, ...

[``Sn]

Serial Number : xxxxxx

[dAtE]

Date of Manufacture : YWW format

[``Pn]

Part Number: scrolls on display

Hardware ID : 114 (RML)

Device Status : OK, Fail

[diAg]

Diagnostics Menu

[FAct]

Factory Page

Part Number

Software Revision

Software Build Number

Serial Number

Date of Manufacture

Hardware ID

Device Status

Device Name

Device Name : EZ-ZONE RM