Watlow EZ-ZONE

®

RML Module

70

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`s2;E]
[ SZ.E]

Math (1 to 16)

Source Zone E

Set the zone of the function

selected above.

0 to 16

0

3538

[offset 70]

0x7D

(125)

1 to 16

0xF (15)

- - - -

25015

uint
RWES

[`S;Lo]
[ S.Lo]

Math (1 to16)

Input Scale Low

This value will correspond

to Output Range Low.

-1,999.000 to 9,999.000

0.0

3556

[offset 70]

0x7D

(125)

1 to16

0x18 (24)

129

25024

float

RWES

[`S;hi]
[ S.hi]

Math (1 to 16)

Input Scale High

This value will correspond

to Output Range High.

-1,999.000 to 9,999.000

1.0

3558

[offset 70]

0x7D

(125)

1 to 16

0x19 (25)

130

25025

float

RWES

[`r;Lo]
[ r.Lo]

Math (1 to 16)

Output Range Low

This value will correspond

to Input Scale Low.

-1,999.000 to 9,999.000

0.0

3560

[offset 70]

0x7D

(125)

1 to 16

0x1A (26)

131

25026

float

RWES

[`r;hi]
[ r.hi]

Math (1 to 16)

Output Range High

This value will correspond

to Input Scale High.

-1,999.000 to 9,999.000

1.0

3562

[offset 70]

0x7D

(125)

1 to 16

0x1B (27)

132

25027

float

RWES

[p;unt]
[P.unt]

Math (1 to 16)

Pressure Units

[`psi]

Pressure Units (1671)

[mbr]

mbar (1672)

[torr]

Torr (1673)

[pasc]

Pascal (1674)

[atm]

Atmosphere (1675)

Pressure

Units

3568

[offset 70]

0x7D

(125)

1 to 16

0x1E (30)

- - - -

25030

uint

RWES

[a;unt]
[A.unt]

Math (1 to 16)

Altitude Units

.

[``ft]

Feet (1674)

[`Hft]

Kilofeet (1671)

Kilofeet

3570

[offset 70]

0x7D

(125)

1 to 16

0x1F (31)

- - - -

25031

uint

RWES

[`FiL]
[ FiL]

Math (1 to 16)

Filter

Filtering smooths out the

output signal of this func-

tion block. Increase the

time to increase filtering.

0.0 to 60.0 seconds

0.0

3564

[offset 70]

0x7D

(125)

1 to 16

0x1C (28)

- - - -

25028

float

RWES

[`uAr]
[`Set]
Variable Menu

[tyPE]
[tyPE]

Variable (1 to 16)

Data Type

Set the variable's data

type.

[AnLg]

Analog (1215)

[`Dig]

Digital (1220)

Analog

9110

[offset 20]

0x66 (102)

1 to 16

1

210

2001

uint
RWES

[Unit]
[Unit]

Variable (1 to 16)

Units

Set the variable's units.

[`A;tp]

Absolute Temperature

(1540)

[`r;tp]

Relative Temperature

(1541)

[PWr]

Power (73)

[`Pro]

Process (75)

[``rh]

Relative Humidity

(1538)

[nonE]

None (61)

Absolute

Temper-

ature

9122

[offset 20]

0x66 (102)

1 to 16

7

- - - -

2007

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set