beautypg.com

Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 119

background image

Watlow EZ-ZONE

®

RML Module

116

Appendix

Indication

Description

Possible Cause(s)

Corrective Action

No Serial Communi-

cation

Cannot establish serial com-

munications with the con-

troller

• Address parameter incorrect

• Incorrect protocol selected

• Baud rate incorrect

• Parity incorrect

• Wiring error

• EIA-485 converter issue

• Incorrect computer or PLC communi-

cations port

• Incorrect software setup

• Wires routed with power cables

• Termination resistor may be required

• Set unique addresses on network

• Match protocol between devices

• Match baud rate between devices

• Match parity between devices

• Correct wiring issue

• Check settings or replace converter

• Set correct communication port

• Correct software setup to match con-

troller

• Route communications wires away

from power wires

• Place 120 Ω resistor across EIA-485

on last controller

Device Error
[`100]

[rEtn]

Controller displays internal

malfunction message at

power up.

• Controller defective

• Sensor input over driven

• Replace or repair controller

• Check sensors for ground loops, re-

verse wiring or out of range values.

Remote User Inter-

face (RUI) menus

inaccessible

Unable to access [`SEt],

[OPEr]

, [FCty] or [ProF]

menus or particular prompts

in Home Page

• Security set to incorrect level

• Check [`loC] settings in Factory Page

• Enter appropriate password in [UloC]

setting in Factory Page

• Digital input set to lockout keypad

• Change state of digital input

• Custom parameters incorrect

• Change custom parameters in Factory

Page

RUI value to low
[ual;l]

Value to low to be displayed

in 4 digit LED display

<-1999

• Incorrect setup

• Check scaling of source data

Detection of and Rules Around Abnormal Sensor Conditions

Inputs

Detection of Abnormal Conditions

Thermocouple

Shorted

No direct detection, Open loop firmware detection.

Open

Yes, Parasitic pull-up

Reversed

Yes, firmware detection

Current Source

Shorted

Range limiting only

Open

Range limiting only

Reversed

Range limiting only

Voltage Source

Open

Range limiting only

Shorted

Range limiting only

Reversed

Range limiting only

RTD

S1 open

Yes, pulled up.

S2 open

Not implemented.

S3 open

Yes, pulled up.

S1 short to S2 Yes, pulled up
S1 short to S3 Yes, pulled down to under range.
S2 shorted to S3 Not implemented, Possible, monitor S2 voltage.
S1 and S2 open Yes, pulled down to under range.
S1 and S3 open Yes, S1 pulled up.

S2 and S3 open Yes pulled up.

Thermistor

S1 open

Yes, pulled up to sensor over range.

S3 open

Yes, pulled up to sensor over range.

S1 short to S3 Yes, pulled down to sensor under range.
S1 and S3 open Yes, S1 pulled up to sensor over range.