beautypg.com

Communications, Low power – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 23

background image

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Watlow EZ-ZONE

®

RML Module

20

Chapter 2 Install and Wire

Limit Module Wiring (RMLx-xxxx-xxxx)

Inputs 1 through 12 Thermocouple

-

+

-

+

-

+

-

+

Thermocouple

S_
R_
S_
R_
S_
R_
S_
R_

Slot A, B, D

• 2K Ω maximum source resistance
• >20 MΩ input impedance
• 3 microampere open-sensor detection
• Thermocouples are polarity sensitive. The negative lead (usually red)

must be connected to S terminal

• To reduce errors, the extension wire for thermocouples must be of the

same alloy as the thermocouple.

Input 1 - 4 (top to bottom): RMLx-(5)xxx-xxxx
Input 5 - 8 (top to bottom): RMLx-x(5)xx-xxxx
Input 9 - 12 (top to bottom): RMLx-xx(5)x-xxxx

CC CA CB CZ CX CY

Slot C

T+ / R+

Modbus

Common

T- / R-

Inter-module Bus

Common

+

-

• CC, CA, CB - Modbus and Standard Bus EIA485 Communi-

cations (selectable via push button under zone address)

• CZ, CX, CY - Inter-module Bus EIA485 Communications
• Do not route network wires with power wires. Connect net-

work wires in daisy-chain fashion when connecting multiple

devices in a network

RML Part # Digit 10 is 1

Communications

CF CD CE CZ CX CY

Slot C

Standard Bus

Common

T- / R-

Inter-module Bus

Common

-

+

T+ / R+

• CF, CD, CE - Standard Bus EIA485 Communications
• CZ, CX, CY - Inter-module Bus EIA485 Communications
• Do not route network wires with power wires. Connect

network wires in daisy-chain fashion when connecting

multiple devices in a network

Communications

RML Part # Digit 10 is A

Low Power

• 20.4 to 30.8 V Å (ac) / Î (dc)
• 47 to 63 Hz
• Module maximum power consumption, 14 VA (ac), 7 VA

(dc)

• 31 Watts maximum power available for P/S part #:0847-

0299-0000

• 60 Watts maximum power available for P/S part #:0847-

0300-0000

• 91 Watts maximum power available for P/S part #:0847-

0301-0000

• Class 2 or SELV power source required to meet UL compli-

ance standards

RML- ALL Model Numbers

98 99

Slot C

power

RML Part # Digits 5, 6, 7