Logic menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 41
Watlow EZ-ZONE
®
RML Module
•
38
•
Chapter 3 Operations Page
RM Limit Module
•
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`LgC]
[oPEr]
Logic Menu
[`Su;A]
[ Su.A]
Logic (1 to 16)
Source Value A
View the value of Source
A.
[`off]
Off (62)
[``on]
On (63)
4678
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x19 (25)
- - - -
27025
uint
R
[`Su;b]
[ Su.b]
Logic (1 to 16)
Source Value B
View the value of Source
B.
[`off]
Off (62)
[``on]
On (63)
4680
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1A (26)
- - - -
27026
uint
R
[`Su;C]
[ Su.C]
Logic (1 to 16)
Source Value C
View the value of Source
C.
[`off]
Off (62)
[``on]
On (63)
4682
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1B (27)
- - - -
27027
uint
R
[`Su;d]
[ Su.d]
Logic (1 to 16)
Source Value D
View the value of Source
D.
[`off]
Off (62)
[``on]
On (63)
4684
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1C (28)
- - - -
27028
uint
R
[`Su;E]
[ Su.E]
Logic (1 to 16)
Source Value E
View the value of Source
E.
[`off]
Off (62)
[``on]
On (63)
4686
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1D (29)
- - - -
27029
uint
R
[`Su;F]
[ Su.F]
Logic (1 to 16)
Source Value F
View the value of Source
F.
[`off]
Off (62)
[``on]
On (63)
4688
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1E (30)
- - - -
27030
uint
R
[`Su;g]
[ Su.g]
Logic (1 to 16)
Value Source G
View the value of Source
G.
[`off]
Off (62)
[``on]
On (63)
4690
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x1F (31)
- - - -
27031
uint
R
[`Su;h]
[ Su.h]
Logic (1 to 16)
Source Value H
View the value of Source
H.
[`off]
Off (62)
[``on]
On (63)
4692
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x20 (32)
- - - -
27032
uint
R
[``o;u]
[ o.v]
Logic (1 to 16)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
4696
[offset 80]
0x7F
(127)
1 to 0x10
(16)
0x22 (34)
- - - -
27034
uint
R
Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EEPROM
S: User Set