Counter menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 40
Watlow EZ-ZONE
®
RML Module
•
37
•
Chapter 3 Operations Page
RM Limit Module
•
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Timer (1 to 16)
Running
Read to determine if timer
is running
Off (62)
On (63)
- - - -
7218
[offset 50]
0x83
(131)
1 to 0x10
(16)
0x0F (15)
- - - -
31015
uint
R
No Dis-
play
Timer (1 to 16)
Output Error
View reported cause for
timer error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
7224
[offset 50]
0x83
(131)
1 to 0x10
(16)
0x12 (18)
- - - -
31018
uint
R
[`Ctr]
[oPEr]
Counter Menu
[`Cnt]
[ Cnt]
Counter (1 to 16)
Count
View the function's total
count.
0 to 9,999
6578
[offset 40]
0x82
(130)
1 to 0x10
(16)
0xF (15)
217
30015
uint
R
[`Su;A]
[ Su.A]
Counter (1 to 16)
Source Value A
View the value of Source
A.
[`off]
Off (62)
[``on]
On (63)
6562
[offset 40]
0x82
(130)
1 to 0x10
(16)
7
- - - -
30007
uint
R
[`Su;b]
[ Su.b]
Counter (1 to 16)
Source Value B
View the value of Source
B.
[`off]
Off (62)
[``on]
On (63)
6564
[offset 40]
0x82
(130)
1 to 0x10
(16)
8
- - - -
30008
uint
R
[``o;u]
[ o.v]
Counter (1 to 16)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
6568
[offset 40]
0x82
(130)
1 to 0x10
(16)
0xA (10)
- - - -
30010
uint
R
No Dis-
play
Counter (1 to 16)
Output Error
View reported cause for
counter error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
6580
[offset 40]
0x82
(130)
1 to 0x10
(16)
0x10 (16)
- - - -
30016
uint
R
Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EEPROM
S: User Set