Power supplies, Dsp30, Dsp60 – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 16: Dsp100, Power supply specifications
Watlow EZ-ZONE
®
RML Module
•
13
•
Chapter 2 Install and Wire
Power Supplies
DSP30
+ + - -
L
N
DC LO
DC OK
1 2 3 4
5
6
53.00 mm
DSP30
2.087 in
91.00 mm 3.583 in
14.20 mm
9.75 mm
43.1 mm
91.00 mm
55.6 mm
49.00 mm
32.10 mm
0.559 in
1.697 in
0.384 in
3.583 in
2.189 in
1.929 in
1.264 in
DSP60
vout ADJ.
+ + - -
L N
DC LO
DC OK
1 2 3 4
5
6
DSP60
71.00 mm
2.795 in
91.00 mm 3.583 in
14.20 mm
9.75 mm
43.1 mm
91.00 mm
55.6 mm
49.00 mm
32.10 mm
0.559 in
1.697 in
0.384 in
3.583 in
2.189 in
1.929 in
1.264 in
DSP100
DC LO
DC OK
vout ADJ.
+ + - -
L N
1 2 3 4
5
6
DSP100
89.9 mm
3.539 in
91.00 mm 3.583 in
5
14.20 mm
9.75 mm
43.1 mm
91.00 mm
56.8 mm
49.00 mm
32.10 mm
0.559 in
1.697 in
0.384 in
3.583 in
2.236 in
1.929 in
1.264 in
Power Supply Specifications
DSP 30
DSP60
DSP100
AC Input Volt-
age Range
VAC
90 - 264VAC, Class II double in-
sulated (No ground connection
required)
Input Fre-
quency
Hz
47 - 63Hz
DC Input Volt-
age range
VDC
120 - 370VDC
Inrush Cur-
rent (115 /
230VAC)
A
25 / 50A
30 / 60A
30 / 60A
Output Volt-
age Accuracy
%
±1% of Nominal
Over voltage
Protection
V
120 - 145%
LED Indica-
tors
- - - -
Green LED = On, Red LED = DC
Output Low
Operating
Temperature
- - - -
-25 to +71°C (Derate linearly
2.5%/°C from 55 to 71°C)
Storage Tem-
perature
- - - -
-25 to +85°C
Operating Hu-
midity
- - - -
20 - 95% RH (non condensing)
Vibration (Op-
erating)
- - - -
IEC 60068-2-6 (Mounting by rail:
Random wave, 10-500 Hz, 2G, ea.
along X, Y, Z axes 10 min/cycle,
60 min)
Safety Agency
Approvals
UL1310 Class 2(1), UL508 Listed,
UL60950-1, EN60950-1, CE
For a comprehensive listing of these specifications point your
browser to :
http://us.tdk-lambda.com/lp/products/dsp-series.htm