Analog input menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 46
Watlow EZ-ZONE
®
RML Module
•
43
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 12)
Sensor Type
Set the analog sensor type
to match the device wired
to this input.
Note:
There is no open-sensor
detection for process
inputs.
[`oFF]
Off (62)
[``tC]
Thermocouple (95)
[`mu]
Millivolts (56)
[uolT]
Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H]
RTD 100 Ω (113)
[r1;0H]
RTD 1,000 Ω (114)
[`Pot]
Potentiometer 1 kΩ
(155)
[thEr]
Thermistor (229)
418
[offset 90]
0x68 (104)
1 to 0xC
(12)
5
3
4005
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 12)
Linearization
Set the linearization to
match the thermocouple
wired to this input.
[```b]
B (11)
[```H]
K (48)
[```C]
C (15)
[```n]
N (58)
[```d]
D (23)
[```r]
R (80)
[```E]
E (26)
[```S]
S (84)
[```F]
F (30)
[```t]
T (93)
[```J]
J (46)
J
420
[offset 90]
0x68 (104)
1 to 0xC
(12)
6
4
4006
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 12)
Units
Set the type of units the
sensor will measure.
[`A;tP]
Absolute Temperature
(1540)
[PWr]
Power (73)
[`Pro]
Process (75)
[``rh]
Relative Humidity
(1538)
Process
492
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x2A (42)
5
4042
uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1 to 12)
Scale Low
Set the low scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range Low output of
this function block.
-100.0 to 1,000.0
0.0
438
[offset 90]
0x68 (104)
1 to 0xC
(12)
0xF (15)
6
4015
float
RWES
[`S;hi]
[ S.hi]
Analog Input (1 to 12)
Scale High
Set the high scale for pro-
cess inputs. This value,
in millivolts, volts or mil-
liamps, will correspond to
the Range High output of
this function block.
-100.0 to 1,000.0
20.0
440
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x10 (16)
7
4016
float
RWES
[`r;Lo]
[ r.Lo]
Analog Input (1 to 12)
Range Low
Set the low range for this
function block's output.
-1,999.000 to 9,999.000
0.0
442
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x11 (17)
8
4017
float
RWES
[`r;hi]
[ r.hi]
Analog Input (1 to 12)
Range High
Set the high range for this
function block's output.
-1,999.000 to 9,999.000
9,999.0
444
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x12 (18)
9
4018
float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 12)
Process Error Enable
Turn the Process Error
Low feature on or off.
[`off]
Off (62)
[Low]
Low (53)
Off
468
[offset 90]
0x68 (104)
1 to 0xC
(12)
0x1E (30)
10
4030
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set