beautypg.com

Analog input menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 46

background image

Watlow EZ-ZONE

®

RML Module

43

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[``Ai]
[`Set]
Analog Input Menu

[`Sen]
[ SEn]

Analog Input (1 to 12)

Sensor Type

Set the analog sensor type

to match the device wired

to this input.

Note:

There is no open-sensor

detection for process

inputs.

[`oFF]

Off (62)

[``tC]

Thermocouple (95)

[`mu]

Millivolts (56)

[uolT]

Volts dc (104)

[`MA]

Milliamps dc (112)

[r0;1H]

RTD 100 Ω (113)

[r1;0H]

RTD 1,000 Ω (114)

[`Pot]

Potentiometer 1 kΩ

(155)

[thEr]

Thermistor (229)

418
[offset 90]

0x68 (104)

1 to 0xC

(12)

5

3

4005

uint
RWES

[`Lin]
[ Lin]

Analog Input (1 to 12)

Linearization

Set the linearization to

match the thermocouple

wired to this input.

[```b]

B (11)

[```H]

K (48)

[```C]

C (15)

[```n]

N (58)

[```d]

D (23)

[```r]

R (80)

[```E]

E (26)

[```S]

S (84)

[```F]

F (30)

[```t]

T (93)

[```J]

J (46)

J

420
[offset 90]

0x68 (104)

1 to 0xC

(12)

6

4

4006

uint
RWES

[Unit]
[Unit]

Analog Input (1 to 12)

Units

Set the type of units the

sensor will measure.

[`A;tP]

Absolute Temperature

(1540)

[PWr]

Power (73)

[`Pro]

Process (75)

[``rh]

Relative Humidity

(1538)

Process

492
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x2A (42)

5

4042

uint
RWES

[`S;Lo]
[ S.Lo]

Analog Input (1 to 12)

Scale Low

Set the low scale for pro-

cess inputs. This value,

in millivolts, volts or mil-

liamps, will correspond to

the Range Low output of

this function block.

-100.0 to 1,000.0

0.0

438
[offset 90]

0x68 (104)

1 to 0xC

(12)

0xF (15)

6

4015

float
RWES

[`S;hi]
[ S.hi]

Analog Input (1 to 12)

Scale High

Set the high scale for pro-

cess inputs. This value,

in millivolts, volts or mil-

liamps, will correspond to

the Range High output of

this function block.

-100.0 to 1,000.0

20.0

440
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x10 (16)

7

4016

float
RWES

[`r;Lo]
[ r.Lo]

Analog Input (1 to 12)

Range Low

Set the low range for this

function block's output.

-1,999.000 to 9,999.000

0.0

442
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x11 (17)

8

4017

float

RWES

[`r;hi]
[ r.hi]

Analog Input (1 to 12)

Range High

Set the high range for this

function block's output.

-1,999.000 to 9,999.000

9,999.0

444
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x12 (18)

9

4018

float

RWES

[`P;EE]
[ P.EE]

Analog Input (1 to 12)

Process Error Enable

Turn the Process Error

Low feature on or off.

[`off]

Off (62)

[Low]

Low (53)

Off

468
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x1E (30)

10

4030

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set