Global menu, Communications menu, Global menu communications menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 74
Watlow EZ-ZONE
®
RML Module
•
71
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`Dig]
[ dig]
Variable (1 to 16)
Digital
Set the variable's value.
[`oFF]
Off (62)
[``on]
On (63)
Off
9112
[offset 20]
0x66 (102)
1 to 0x10
(16)
2
211
2002
uint
RWES
[anLg]
[AnLg]
Variable (1 to 16)
Analog
Set the variable's value.
-1,999.000 to 9,999.000
Note:
Stored in °F only
0.0
9114
[offset 20]
0x66 (102)
1 to 0x10
(16)
3
212
2003
float
RWES
No Dis-
play
Variable (1 to 16)
Output Value
Off (62)
On (63)
-1,999.000 to 9,999.000
- - - -
9116
[offset 20]
0x66 (102)
1 to 0x10
(16)
4
- - - -
2004
float
R
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
368
0x67 (103)
1
5
110
3005
uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the ap-
plied ac line power source.
[``50]
50 Hz (3)
[``60]
60 Hz (4)
60 Hz
- - - -
0x65 (101)
1
0x22 (34)
- - - -
1034
uint
RWES
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of Dis-
play Pairs.
1 to 15
2
- - - -
0x67 (103)
1
0x1C (28)
- - - -
3028
uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this controller's
settings to the selected
set.
[none]
None (61)-
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
None
26
0x65 (101)
1
0x0E (14)
118
1014
uint
RWE
[USr;r]
[USr.r]
Global
User Restore Settings
Replace all of this control-
ler's settings with another
set.
[none]
None (61)
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
[FCty]
Factory (31)
None
24
0x65 (101)
1
0x0D (13)
117
1013
uint
RWE
[CoM]
[`SEt]
Communications Menu
[bAUd]
[bAUd]
Communications
Baud Rate
Set the speed of this con-
troller's communications
to match the speed of the
serial network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600
3494
0x96 (150)
1
3
- - - -
17002
uint
RWE
[`PAr]
[ PAr]
Communications
Parity
Set the parity of this con-
troller to match the parity
of the serial network.
[none]
None (61)
[EuEn]
Even (191)
[`odd]
Odd (192)
None
3496
0x96 (150)
1
4
- - - -
17003
uint
RWE
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set