Alarm menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 37
Watlow EZ-ZONE
®
RML Module
•
34
•
Chapter 3 Operations Page
RM Limit Module
•
Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Limit (1 to 12)
Clear Request
Clear limit once limit con-
dition is cleared.
Clear (0)
No Change (255)
- - - -
1490
[offset 30]
0x70 (112)
1 to 0xC
(12)
1
- - - -
12001
uint
RW
No Dis-
play
Limit (1 to 12)
Status
Reflects whether or not
the limit is in a safe or
failed mode..
Fail (32)
Safe (1667)
- - - -
1500
[offset 30]
0x70 (112)
1 to 0xC
(12)
0x0D (13)
- - - -
12013
uint
R
No Dis-
play
Limit (1 to 12)
Output Value
Current output state.
On (63)
Off (62)
- - - -
1502
[offset 30]
0x70 (112)
1 to 0xC
(12)
7
- - - -
12007
uint
R
[ALM]
[oPEr]
Alarm Menu
[`A;Lo]
[ A.Lo]
Alarm (1 to 16)
Low Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger a
low alarm.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
32.0°F
or
units
0.0°C
2532
[offset 60]
0x6D
(109)
1 to 0x10
(16)
2
18
9002
float
RWES
[`A;hi]
[ A.hi]
Alarm (1 to 16)
High Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger a
high alarm.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
300.0°F
or
units
150.0°C
2530
[offset 60]
0x6D
(109)
1 to 0x10
(16)
1
19
9001
float
RWES
[A;Clr]
[ A.hi]
Alarm (1 to 16)
Clear Request
Write to this register to
clear an alarm
Clear (129)
Ignore (204)
Ignore
- - - -
- - - -
- - - -
9026
uint
RW
[A;sir]
[A.Sir]
Alarm (1 to 16)
Silence Request
Write to this register to
silence an alarm
Ignore (204)
Silence (108)
Ignore
- - - -
- - - -
- - - -
9027
uint
RW
[`A;st]
[ A.St]
Alarm (1 to 16)
State
Current state of alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
Startup
2546
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x0A (10)
- - - -
9009
uint
R
No Dis-
play
Alarm (1 to 16)
Latched
Read this register to de-
termine if the alarm is
latched
No (59)
Yes (106)
No
2548
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x0A (10)
- - - -
9010
uint
R
No Dis-
play
Alarm (1 to 16)
Silenced
Read this register to de-
termine if the alarm is
silenced
No (59)
Yes (106)
None
2550
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x0B (11)
- - - -
9011
uint
R
Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EEPROM
S: User Set