Troubleshooting Alarms, Errors and Module Issues

Indication

Description

Possible Cause(s)

Corrective Action

Alarm won’t clear or

reset

Alarm will not clear or reset

with keypad or digital input

• Alarm latching is active

• Alarm set to incorrect output

• Alarm is set to incorrect source

• Sensor input is out of alarm set point

range

• Alarm set point is incorrect

• Alarm is set to incorrect type

• Digital input function is incorrect

• Reset alarm when process is within

range or disable latching

• Set output to correct alarm source

instance

• Set alarm source to correct input in-

stance

• Correct cause of sensor input out of

alarm range

• Set alarm set point to correct trip

point

• Set alarm to correct type: process, de-

viation or power

• Set digital input function and source

instance

Alarm won’t occur

Alarm will not activate output • Alarm silencing is active

• Alarm blocking is active

• Alarm is set to incorrect output

• Alarm is set to incorrect source

• Alarm set point is incorrect

• Alarm is set to incorrect type

• Disable alarm silencing, if required

• Disable alarm blocking, if required

• Set output to correct alarm source

instance

• Set alarm source to correct input in-

stance

• Set alarm set point to correct trip

point

• Set alarm to correct type: process, de-

viation or power

Alarm Error
[AL;E1]

[AL;E2]

[AL;E3]

[AL;E4]

[AL;E5]

[AL;E6]

[AL;E7]

[AL;E8]

[AL;E9]

[AL;10]

[AL;11]

[AL;12]

[AL;13]

[AL;14]

[AL;15]

[AL;16]

Alarm state cannot be deter-

mined due to lack of sensor

input

• Sensor improperly wired or open

• Incorrect setting of sensor type

• Calibration corrupt

• Correct wiring or replace sensor

• Match setting to sensor used

• Check calibration of controller

Alarm Low
[AL;L1]

[AL;L2]

[AL;L3]

[AL;L4]

[AL;L5]

[AL;L6]

[AL;L7]

[AL;L8]

[AL;L9] [AL;10]

[AL;11]

[AL;12]

[AL;13]

[AL;14]

[AL;15]

[AL;16]

Sensor input below low alarm

set point

• Temperature is less than alarm set

point

• Alarm is set to latching and an alarm

occurred in the past

• Incorrect alarm set point

• Incorrect alarm source

• Check cause of under temperature

• Clear latched alarm

• Establish correct alarm set point

• Set alarm source to proper setting

Alarm High
[AL;h1}

[AL;h2]

[AL;h3]

[AL;h4]

[AL;h5}

[AL;h6]

[AL;h7]

[AL;h8]

[AL;h9] [AL;10]

[AL;11]

[AL;12]

[AL;13]

[AL;14]

[AL;15]

[AL;16]

Sensor input above high

alarm set point

• Temperature is greater than alarm

set point

• Alarm is set to latching and an alarm

occurred in the past

• Incorrect alarm set point

• Incorrect alarm source

• Check cause of over temperature

• Clear latched alarm

• Establish correct alarm set point

• Set alarm source to proper setting

No Display

No display indication or LED

illumination

• Power to controller is off

• Fuse open

• Breaker tripped

• Safety interlock switch open

• Separate system limit control acti-

vated

• Wiring error

• Incorrect voltage to controller

• Turn on power

• Replace fuse

• Reset breaker

• Close interlock switch

• Reset limit

• Correct wiring issue

• Apply correct voltage, check part

number