Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 61
Watlow EZ-ZONE
®
RML Module
•
58
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;B]
[SFn.b]
Counter (1 to 16)
Source Function B
Set the type of function
that will be used for the
counter load signal.
[nonE]
None (61)
[ALM]
Alarm Reset (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
6552
[offset 40]
0x82 (130)
1 to 16
2
- - - -
30002
uint
RWES
[`Si;B]
[ Si.b]
Counter (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250
1
6556
[offset 40]
0x82 (130)
1 to 16
4
- - - -
30004
uint
RWES
[`S2;B]
[ SZ.b]
Counter (1 to 16)
Source Zone B
Set the zone of the function
selected above.
0 to 16
0
6560
[offset 40]
0x82 (130)
1 to 16
6
- - - -
30006
uint
RWES
[sas;b]
[SAS.b]
Counter (1 to 16)
Source Active State B
Set what output state will
indicate on.
[high]
High (37)
[LoW]
Low (53)
High
6572
[offset 40]
0x82 (130)
1 to 16
0xC (12)
- - - -
30012
uint
RWES
[LoAd]
[LoAd]
Counter (1 to 16)
Load Value
Set the counter's initial
value.
0 to 9,999
0
6574
[offset 40]
0x82 (130)
1 to 16
(13)
215
30013
uint
RWES
[trgt]
[trgt]
Counter (1 to 16)
Target Value
Set the value that will turn
the output value on.
0 to 9,999
9,999
6576
[offset 40]
0x82 (130)
1 to 16
0xE (14)
216
30014
uint
RWES
[`lAt]
[ LAt]
Counter (1 to 16)
Latching
If enabled, output will latch
when count equals target
value.
No (59)
Yes (106)
No
6582
[offset 40]
0x82 (130)
1 to 16
0x11 (17)
218
30017
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set