Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 57
Watlow EZ-ZONE
®
RML Module
•
54
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;A]
[SFn.A]
Compare (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop
(73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed,
Control Loop (242)
[`SP;o]
Set Point Open, Con-
trol Loop (243)
[`uAr]
Variable (245)
None
5910
[offset 40]
0x80 (128)
1 to 16
1
- - - -
28001
uint
RWES
[`Si;A]
[ Si.A]
Compare (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250
1
5914
[offset 40]
0x80 (128)
1 to 16
3
- - - -
28003
uint
RWES
[`S2;A]
[ SZ.A]
Compare (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
5918
[offset 40]
0x80 (128)
1 to 16
5
- - - -
28005
uint
RWES
[SFn;B]
[SFn.b]
Compare (1 to 16)
Source Function B
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop
(73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed,
Control Loop (242)
[`SP;o]
Set Point Open, Con-
trol Loop (243)
[`uAr]
Variable (245)
None
5912
[offset 40]
0x80 (128)
1 to 16
2
- - - -
28002
uint
RWES
[`Si;B]
[ Si.b]
Compare (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250
1
5916
[offset 40]
0x80 (128)
1 to 16
4
- - - -
28004
uint
RWES
[`S2;B]
[ SZ.b]
Compare (1 to 16)
Source Zone B
Set thezone of the function
selected above.
0 to 16
0
5920
[offset 40]
0x80 (128)
1 to 16
6
- - - -
28006
uint
RWES
[`Er;h]
[ Er.h]
Compare (1 to 16)
Error Handling
[``t;g]
True Good (1476)
[``t;b]
True Bad (1477)
[``F;g]
False Good (1478)
[``F;b]
False Bad (1479)
False Bad 5932
[offset 40]
0x80 (128)
1 to 16
0xC (12)
- - - -
28012
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set