beautypg.com

Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 57

background image

Watlow EZ-ZONE

®

RML Module

54

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[SFn;A]
[SFn.A]

Compare (1 to 16)

Source Function A

Set the type of function

that will be used for this

source.

[nonE]

None (61)

[``Ai]

Analog Input (142)

[CUrr]

Current (22)

[`C;Pr]

Cool Power, Control

Loop (161)

[`h;Pr]

Heat Power, Control

Loop (160)

[PWr]

Power, Control Loop

(73)

[`Lnr]

Linearization (238)

[MAt]

Math (240)

[``Pu]

Process Value (241)

[`SP;C]

Set Point Closed,

Control Loop (242)

[`SP;o]

Set Point Open, Con-

trol Loop (243)

[`uAr]

Variable (245)

None

5910

[offset 40]

0x80 (128)

1 to 16

1

- - - -

28001

uint
RWES

[`Si;A]
[ Si.A]

Compare (1 to 16)

Source Instance A

Set the instance of the

function selected above.

1 to 250

1

5914

[offset 40]

0x80 (128)

1 to 16

3

- - - -

28003

uint
RWES

[`S2;A]
[ SZ.A]

Compare (1 to 16)

Source Zone A

Set the zone of the function

selected above.

0 to 16

0

5918

[offset 40]

0x80 (128)

1 to 16

5

- - - -

28005

uint
RWES

[SFn;B]
[SFn.b]

Compare (1 to 16)

Source Function B

Set the type of function

that will be used for this

source.

[nonE]

None (61)

[``Ai]

Analog Input (142)

[CUrr]

Current (22)

[`C;Pr]

Cool Power, Control

Loop (161)

[`h;Pr]

Heat Power, Control

Loop (160)

[PWr]

Power, Control Loop

(73)

[`Lnr]

Linearization (238)

[MAt]

Math (240)

[``Pu]

Process Value (241)

[`SP;C]

Set Point Closed,

Control Loop (242)

[`SP;o]

Set Point Open, Con-

trol Loop (243)

[`uAr]

Variable (245)

None

5912

[offset 40]

0x80 (128)

1 to 16

2

- - - -

28002

uint
RWES

[`Si;B]
[ Si.b]

Compare (1 to 16)

Source Instance B

Set the instance of the

function selected above.

1 to 250

1

5916

[offset 40]

0x80 (128)

1 to 16

4

- - - -

28004

uint
RWES

[`S2;B]
[ SZ.b]

Compare (1 to 16)

Source Zone B

Set thezone of the function

selected above.

0 to 16

0

5920

[offset 40]

0x80 (128)

1 to 16

6

- - - -

28006

uint
RWES

[`Er;h]
[ Er.h]

Compare (1 to 16)

Error Handling

[``t;g]

True Good (1476)

[``t;b]

True Bad (1477)

[``F;g]

False Good (1478)

[``F;b]

False Bad (1479)

False Bad 5932

[offset 40]

0x80 (128)

1 to 16

0xC (12)

- - - -

28012

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set