Math menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 70
Watlow EZ-ZONE
®
RML Module
•
67
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[MAt]
[`Set]
Math Menu
[``Fn]
[ Fn]
Math (1 to 16)
Function
Set the operator that will
be applied to the sources.
[`oFF]
Off (62)
[`Aug]
Average (1367)
[`P;SC]
Process Scale (1371)
[`d;SC]
Deviation Scale
(1372)
[``s;o]
Switch Over (1370)
[diFF]
Differential (1373)
[rAti]
Ratio (1374)
[`Add]
Add (1375)
[MUL]
Multiply (1376)
[A;diF]
Absolute Difference
(1377)
[Min]
Minimum (1378)
[MAH]
Maximum (1379)
[root]
Square Root (1380)
[hoLd]
Sample and Hold
(1381)
[`alt]
Altitude (1349)
[dew]
Dewpoint (1650)
Off
3550
[offset 70]
0x7D
(125)
1 to 16
0x15 (21)
128
25021
uint
RWES
[SFn;A]
[SFn.A]
Math (1 to 16)
Source Function A
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop
(73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed,
Control Loop (242)
[`SP;o]
Set Point Open, Con-
trol Loop (243)
[`uAr]
Variable (245)
None
3510
[offset 70]
0x7D
(125)
1 to 16
1
- - - -
25001
uint
RWES
[`Si;A]
[ Si.A]
Math (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250
1
3520
[offset 70]
0x7D
(125)
1 to 16
6
- - - -
25006
uint
RWES
[`S2;A]
[ SZ.A]
Math (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
3530
[offset 70]
0x7D
(125)
1 to 16
0xB (11)
- - - -
25011
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set