Watlow EZ-ZONE

®

RML Module

32

Chapter 3 Operations Page

RM Limit Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[``Ai]
[oPEr]
Analog Input Menu

[``Ain]
[ Ain]

Analog Input (1 to 12)

Process Value

View the process value.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

410

[offset 90]

0x68 (104)

1 to 0x0C

(12)

1

0

4001

float

R

[``pu;f]
[ Pu.F]

Analog Input (1 to 12)

Filtered Process Value

View the process value

when filtering is turned

on..

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

452

[offset 90]

0x68 (104)

1 to 0x0C

(12)

0x16 (22)

- - - -

4022

float

R

[`i;Er]
[ i.Er]

Analog Input (1 to 12)

Error Status

View the cause of the most

recent error. If the [Attn]

message is [Er;i1] or
[Er;i2]

, this parameter

will display the cause of

the input error.

[nonE]

None (61)

[OPEn]

Open (65)

[Shrt]

Shorted (127)

[`E;M]

Measurement Error

(140)

[E;CAL]

Bad Calibration

Data (139)

[Er;Ab]

Ambient Error (9)

[E;;Rtd]

RTD Error (141)

[FAiL]

Fail (32)

[Nsrc]

Not Sourced (246)

None

412

[offset 90]

0x68 (104)

1 to 0x0C

(12)

2

1

4002

uint

R

[`i;Ca]
[ i.CA]

Analog Input (1 to 12)

Calibration Offset

Offset the input reading to

compensate for lead wire

resistance or other factors

that cause the input read-

ing to vary from the actual

process value.

-1,999.000 to 9,999.000°F

or units

-1,110.555 to 5,555.000°C

0.0

432

[offset 90]

0x68 (104)

1 to 0x0C

(12)

0xC (12)

2

4012

float

RWES

No Dis-

play

Analog Input (1 to 12)

Clear Latched Input Er-

ror

Clear latched input when

input error condition no

longer exists.

Clear Latch (1221)

- - - -

466

[offset 90]

0x68 (104)

1 to 0x0C

(12)

0x1D (29)

- - - -

4029

uint

RW

[`dio]
[oPEr]
Digital Input/Output Menu

[`do;S]
[ do.S]

Digital Output (1 to 8)

Output State

View the state of this out-

put.

[`off]

Off (62)

[``on]

On (63)

1862

[offset 30]

0x6A (106)

1 to 8

7

90

6007

uint

R

[`di;S]
[ di.S]

Digital Input (1 to 6 and 9)

Input State

View this event input state.

[`off]

Off (62)

[``on]

On (63)

1870

[offset 30]

0x6A (106)

1 to 6

and 9

0xB (11)

- - - -

6011

uint

R

No Dis-

play

Digital Input (1 to 6 and 9)

Source Value A

View the value of source A

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

- - - -

1874

[offset 30]

0x6A (106)

1 to 9

0x0D (13)

- - - -

6013

float

R

Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM