Watlow EZ-ZONE

®

RML Module

77

Chapter 5 Factory Page

RM Limit Module • Factory Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[ELi;S]
[ELi.S]

Calibration Menu (1 to 12)

Electrical Input Slope

Adjust this value to calibrate

the slope of the input value.

-1,999.000 to 9,999.000

1.0

430

[offset

90]

0x68

(104)

1 to 0x0C

(12)

0xB (11)

- - - -

4011

float

RWES

Note: Some values will be rounded off to fit in the four-character display . Full values can
be read with another interface .

If there is only one instance of a menu, no submenus will appear .