Limit menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 50
![background image](/manuals/359088/50/background.png)
Watlow EZ-ZONE
®
RML Module
•
47
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`Si;A]
[ Si.A]
Action (1 to 16)
Source Instance A
Set the instance of the
function selected above.
1 to 250
1
2212
[offset 20]
0x6E
(110)
1 to 16
2
- - - -
10002
uint
RWES
[`S2;A]
[ SZ.A]
Action (1 to 16)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
2222
[offset 20]
0x6E
(110)
1 to 16
7
- - - -
10007
uint
RWES
[`LEu]
[ LEv]
Action (1 to 16)
Active Level
Set the action that will be
considered a true state.
[LoW]
Low (53)
[high]
High (37)
High
2230
[offset 20]
0x6E
(110)
1 to 16
1
137
10001
uint
RWES
[Lim]
[`Set]
Limit Menu
[`L;Sd]
[ L.Sd]
Limit (1 to 12)
Sides
Select which side or sides
of the process value will be
monitored.
[both]
Both (13)
[high]
High (37)
[LoW]
Low (53)
Both
1498
[offset 30]
0x70 (112)
1 to 12
5
40
12005
uint
RWES
[`L;hy]
[ L.hy]
Limit (1 to 12)
Hysteresis
Set the hysteresis for the
limit function. This deter-
mines how far into the safe
range the process value
must move before the limit
can be cleared.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
3.0°F or
units
2.0°C
1492
[offset 30]
0x70 (112)
1 to 12
2
41
12002
float
RWES
[SP;Lh]
[SP.Lh]
Limit (1 to 12)
Set Point Limit High
Set the high end of the
limit set point range.
-1,999.000 to 9,999.000
9,999.000 1506
[offset 30]
0x70 (112)
1 to 12
9
39
12009
float
RWES
[SP;Ll]
[SP.LL]
Limit (1 to 12)
Set Point Limit Low
Set the low end of the limit
set point range.
-1,999.000 to 9,999.000
-1,999.000 1508
[offset 30]
0x70 (112)
1 to 12
0xA (10)
38
12010
float
RWES
[`Lh;S]
[ Lh.S]
Limit (1 to 12)
High Set Point
Set the high process value
that will trigger the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1496
[offset 30]
0x70 (112)
1 to 12
4
42
12004
float
RWES
[`LL;S]
[ LL.S]
Limit (1 to 12)
Low Set Point
Set the low process value
that will trigger the limit.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
1494
[offset 30]
0x70 (112)
1 to 12
3
43
12003
float
RWES
[SFn;A]
[SFn.A]
Limit (1 to 12)
Source Function A
Set the source for the limit
reset function.
[nonE]
None (61)
[`dio]
Digital I/O (1142)
[`FUn]
Function Key (1001)
[`uAr]
Variable (245)
None
- - - -
0x70 (112)
1 to 12
0x0F (15)
- - - -
12015
uint
RWES
[`Si;A]
[ Si.A]
Limit (1 to 12)
Source Instance A
Set the instance of the
function selected above.
1 or 250
1
- - - -
0x70 (112)
1 to 12
0x10 (16)
- - - -
12016
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .