Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`Si;A]
[ Si.A]

Action (1 to 16)

Source Instance A

Set the instance of the

function selected above.

1 to 250

1

2212
[offset 20]

0x6E

(110)

1 to 16

2

- - - -

10002

uint
RWES

[`S2;A]
[ SZ.A]

Action (1 to 16)

Source Zone A

Set the zone of the function

selected above.

0 to 16

0

2222
[offset 20]

0x6E

(110)

1 to 16

7

- - - -

10007

uint
RWES

[`LEu]
[ LEv]

Action (1 to 16)

Active Level

Set the action that will be

considered a true state.

[LoW]

Low (53)

[high]

High (37)

High

2230
[offset 20]

0x6E

(110)

1 to 16

1

137

10001

uint
RWES

[Lim]
[`Set]
Limit Menu

[`L;Sd]
[ L.Sd]

Limit (1 to 12)

Sides

Select which side or sides

of the process value will be

monitored.

[both]

Both (13)

[high]

High (37)

[LoW]

Low (53)

Both

1498

[offset 30]

0x70 (112)

1 to 12

5

40

12005

uint

RWES

[`L;hy]
[ L.hy]

Limit (1 to 12)

Hysteresis

Set the hysteresis for the

limit function. This deter-

mines how far into the safe

range the process value

must move before the limit

can be cleared.

0.001 to 9,999.000°F or units
0.001 to 5,555.000°C

3.0°F or

units

2.0°C

1492

[offset 30]

0x70 (112)

1 to 12

2

41

12002

float

RWES

[SP;Lh]
[SP.Lh]

Limit (1 to 12)

Set Point Limit High

Set the high end of the

limit set point range.

-1,999.000 to 9,999.000

9,999.000 1506

[offset 30]

0x70 (112)

1 to 12

9

39

12009

float

RWES

[SP;Ll]
[SP.LL]

Limit (1 to 12)

Set Point Limit Low

Set the low end of the limit

set point range.

-1,999.000 to 9,999.000

-1,999.000 1508

[offset 30]

0x70 (112)

1 to 12

0xA (10)

38

12010

float

RWES

[`Lh;S]
[ Lh.S]

Limit (1 to 12)

High Set Point

Set the high process value

that will trigger the limit.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

1496

[offset 30]

0x70 (112)

1 to 12

4

42

12004

float

RWES

[`LL;S]
[ LL.S]

Limit (1 to 12)

Low Set Point

Set the low process value

that will trigger the limit.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

1494

[offset 30]

0x70 (112)

1 to 12

3

43

12003

float

RWES

[SFn;A]
[SFn.A]

Limit (1 to 12)

Source Function A

Set the source for the limit

reset function.

[nonE]

None (61)

[`dio]

Digital I/O (1142)

[`FUn]

Function Key (1001)

[`uAr]

Variable (245)

None

- - - -

0x70 (112)

1 to 12

0x0F (15)

- - - -

12015

uint
RWES

[`Si;A]
[ Si.A]

Limit (1 to 12)

Source Instance A

Set the instance of the

function selected above.

1 or 250

1

- - - -

0x70 (112)

1 to 12

0x10 (16)

- - - -

12016

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set