beautypg.com

Linearization menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 38

background image

Watlow EZ-ZONE

®

RML Module

35

Chapter 3 Operations Page

RM Limit Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

No Dis-

play

Alarm (1 to 16)

Clearable

Read to determine if an

alarm can be cleared

No (59)
Yes (106)

None

2552
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0xC (12)

- - - -

9012

uint

R

No Dis-

play

Alarm (1 to 16)

Clear Request

Write to this register to

clear an alarm

Clear (0)
No Change (255)

None

2554
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0xD (13)

32

9013

uint

RW

No Dis-

play

Alarm (1 to 16)

Silence Request

Write to this register to

silence an alarm

Clear (0)
No Change (255)

None

2556
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x0E (14)

33

9014

uint

RW

No Dis-

play

Alarm (1 to 16)

Working Process Value

Process value used by

alarms

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

None

2566
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x13 (19)

- - - -

9019

float

R

No Dis-

play

Alarm (1 to 16)

Output Value

Current state of alarm

output

On (63)

Off (62)

None

2576
[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x18 (24)

- - - -

9024

uint

R

[`Lnr]
[oPEr]
Linearization Menu

[`Su;A]
[ Su.A]

Linearization (1 to 12)

Source Value A

View the value of Source

A.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

7996
[offset 70]

0x86

(134)

1 to 0x10

(16)

4

- - - -

34004

float
R

[oFSt]
[oFSt]

Linearization (1 to 12)

Offset

Set an offset to be applied

to this function's output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0

8000
[offset 70]

0x86

(134)

1 to 0x10

(16)

6

- - - -

34006

float
RWES

[``o;u]
[ o.v]

Linearization (1 to 12)

Output Value

View the value of this

function's output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

8002
[offset 70]

0x86

(134)

1 to 0x10

(16)

7

- - - -

34007

float
R

No Dis-

play

Linearization (1 to 12)

Output Error

View reported cause for

linearization error

None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)

8044
[offset 70]

0x86

(134)

1 to 0x10

(16)

0x1C (28)

- - - -

34028

uint

R

Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set