Watlow EZ-ZONE

®

RML Module

21

Chapter 2 Install and Wire

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Inputs 1 through 12 Thermistor

• >20 MΩ input impedance

Input 1 - 4 (top to bottom): RMLx-(6)xxx-xxxx
Input 5 - 8 (top to bottom): RMLx-x(6)xx-xxxx
Input 9 - 12 (top to bottom): RMLx-xx(6)x-xxxx

Thermistor

S_
R_
S_
R_
S_
R_
S_
R_

Slot A, B, D

RML Part # Digits 5, 6, 7

Inputs 1 through 12 RTD

2-wire

RTD

S_
R_
S_
R_
S_
R_
S_
R_

Slot A, B, D

• platinum, 100 and 1,000 Ω @ 0°C
• calibration to DIN curve (0.00385 Ω/Ω/°C)
• 20 Ω total lead resistance
• RTD excitation current of 0.09 mA typical.

Each ohm of lead resistance may affect the

reading by 2.55°C.

Input 1 - 4 (top to bottom): RMLx-(5)xxx-

xxxx

Input 5 - 8 (top to bottom): RMLx-x(5)xx-

xxxx

Input 9 - 12 (top to bottom): RMLx-xx(5)x-

xxxx

RML Part # Digits 5, 6, 7

Common

DC Input

B1
D1
D2
D3
D4
D5
D6
Z1

Slot D

Supply

DC Input

DC Input

DC Input

DC Input

DC Input

Internal

Digital Input Event Condi-

tions

• Dry Contact
- Input inactive when >

100KΩ

- Input active when < 50Ω
• Voltage
- Input inactive when < 2V
- Input active when > 3V
• Six user configurable digital

inputs/outputs per slot

- Slot D DI 1 - 6 RMLx-x(C)

xx-xxxx

- Slot E DI 9 RMLx-xxx(B)-

xxxx

Note:

When using a dry contact

with Digital Input 9 (Slot E),

notice that the connection is

made between pins B9 and

D9.

RML Part # Digit 7, 8 is C and or B Respectively

Digital Inputs 1 through 6 and 9

Common

DC Input

B9
D9

Slot E

B

common

Vdc

D

_

_

D

_

24 Vdc

_

Z

Voltage Input

AWG Ohms/1000ft

14

2.575

16

4.094

18

6.510

20

10.35

22

16.46

24

26.17

26

41.62

28

66.17

D

_

24 Vdc

_

B

Dry Contact

Slot E

Slot D