Output menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 51

background image

Watlow EZ-ZONE

®

RML Module

48

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`S2;A]
[ SZ.A]

Limit (1 to 12)

Source Zone A

Set the zone of the function

selected above.

0 or 16

0

- - - -

0x70 (112)

1 to 0xC

(12)

0x11 (17)

- - - -

12017

uint
RWES

[`lCr]
[ LCr]

Limit (1 to 12)

Limit Clear

Clear the specified limit if

limit condition no longer

exists.

[`Clr]

Clear (129)

[ignr]

Ignore (204)

Ignore

1516

[offset 30]

0x70 (112)

1 to 0xC

(12)

0x0E (14)

- - - -

12014

uint

R

[`l;st]
[ L.St]

Limit (1 to 12)

Limit Status

Current state of limit.

[fail]

Fail (32)

[safe]

Safe (1667)

- - - -

1500

[offset 30]

0x70 (112)

1 to 0xC

(12)

6

- - - -

12013

uint
R

[otpt]
[`Set]
Output Menu

[``Fn]
[ Fn]

Output (1 to 4 and 7 - 10)

Function

Select what function will

drive this output.

Note:

Output 8 is set by default

(factory settings) to mod-

ule limit

[`oFF]

Off (62)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[`FUn]

Function Key (1001)

[`lnr]

Linearization (238)

[`LgC]

Logic (239)

[mat]

Math (240)

[tMr]

Timer (244)

[`uAr]

Variable (245)

[m;li]

Module Limit (1696)

[LiM]

Limit (126)

off

1858
[offset 30]

0x6A

(106)

1 to 0xA

(10)

5

96

6005

uint
RWES

[``Fi]
[ Fi]

Output (1 to 4 and 7 - 10)

Function Instance

Set the instance of the

function selected above.

1 to 24

1

1860
[offset 30]

0x6A

(106)

1 to 0xA

(10)

6

- - - -

6006

uint
RWES

[`S2;A]
[ SZ.A]

Output (1 to 4 and 7 - 10)

Source Zone A

Set the instance of the

function selected above.

1 to 16

0

1872
[offset 30]

0x6A

(106)

1 to 0xA

(10)

0xC (12)

- - - -

6012

uint
RWES

[`o;Ct]
[ o.Ct]

Output (1 to 4 and 7 - 10)

Control

Set the output control type.

This parameter is only

used with PID control, but

can be set anytime.

[`Ftb]

Fixed Time Base (34)

[`utb]

Variable Time Base

(103)

Fixed

Time

Base

1852
[offset 30]

0x6A

(106)

1 to (12)

2

- - - -

6002

uint
RWES

[`o;tb]
[ o.tb]

Output (1 to 4 and 7 - 10)

Time Base

Set the time base for fixed-

time-base control.

0.1 to 60.0 seconds (solid-

state relay or switched dc)

5.0 to 60.0 seconds (mechani-

cal relay or no-arc power

control)

0.1 sec.

[SSR &

sw dc]

20.0 sec.

[mech,

relay, no-

arc]

1854
[offset 30]

0x6A

(106)

1 to (12)

3

- - - -

6003

float
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set