beautypg.com

A conceptual view of the rml – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 8

background image

Watlow EZ-ZONE

®

RML Module

5

Chapter 1 Overview

A Conceptual View of the RML

The flexibility of the RML’s software and hardware

allows for variation in configurations. Acquiring a

better understanding of its functionality and capa-

bilities while at the same time planning out how the

controller can be used will deliver maximum effec-

tiveness in your application.

It is useful to think of the controller in three

parts: inputs, procedures and outputs. Information

flows from an input to a procedure to an output when

the controller is properly configured. An RML con-

troller can carry out several procedures at the same

time, e.g., monitoring for several different alarm situ-

ations, monitoring and acting upon digital inputs and

driving output devices such as audible alarms, lights

and contactors. Each process needs to be thought out

carefully and the controller’s inputs, procedures and

outputs set up properly.

Inputs

The inputs provide the information that any given

programmed procedure can act upon. Simply stated,

this information may come from an operator pushing

a button or from a sensor monitoring the tempera-

ture of a part being heated or cooled.

Each analog input typically uses a thermocouple,

RTD or thermistor to read the process temperature.

It can also read volts, current or resistance, allowing

it to use various devices to read humidity, air pres-

sure, operator inputs and others values. The settings

in the Analog Input Menu (Setup Page) for each ana-

log input must be configured to match the device con-

nected to that input.

Each digital input reads whether a device is active

or inactive. An RML equipped with digital input/out-

put hardware includes two sets of terminals where

each of which can be used as either an input or an

output. Each pair of terminals must be configured

to function as either an input or output with the di-

rection parameter in the Digital Input/Output Menu

(Setup Page).

Functions

Functions use input signals to calculate a value. A

function may be as simple as reading a digital input

to set a state to true or false, or reading a tempera-

ture to set an alarm state to on or off. Alternatively,

if a failure with the primary sensing device should

occur the limit could trip a contactor removing power

from the heating element to avoid damaging the load.

To set up a function, it’s important to tell it what

source, or instance, to use. For example, if the control

is equipped with digital inputs they can be config-

ured to reset an individual alarm or all alarms. If

configured as such, the next step would be to define

which of the available digital inputs would be tied to

the alarm reset function. The RML module can be

equipped with up to 7 digital inputs, instance 1 - 6

and or 9. Once the specific input has been selected

simply assign the alarm reset function to it (Setup

Page, DIO Menu). The last step would be to define

the alarm instance that should be reset. If zero is en-

tered for the alarm instance when the digital input

selected above is enabled, all latched alarms without

a currently existing alarm condition will be reset. If

a specific alarm instance (1 -16) is selected it will be

that instance alone that will be reset.

Note:

Alarms will reset automatically when the condition

that caused the alarm goes back to a non-alarm

state if the alarm latching prompt is set to non-

latching (Setup Page, ALM Menu).

Keep in mind that a function is a user-programmed

internal process that does not execute any action out-

side of the controller. To have any effect outside of the

controller, an output must be configured to respond

to a function.

Outputs

Outputs can perform various functions or actions in

response to information provided by a function, such

as removal of the control voltage to a contactor; turn-

ing a light on or off; unlocking a door; or turning on

an audible alarm.

Assign an output to a function in the Output

Menu or Digital Input/Output Menu. Then select

which instance of that function will drive the select-

ed output. For example, in using a Limit Control an

output can be configured to respond to an alarm, i.g.,

(instance 15) or to a limit condition.

You can assign more than one output to respond

to a single instance of a function. For example, alarm

2 could be used to trigger a light connected to output

1 and a siren connected to digital output 5.

Input Events and Output Events

Input events are internal states that are set by the

digital inputs. Digital Input 1 provides the state of

input event 1, and Digital Input 2 provides the state

of input event 2. The setting of Digital Input Func-

tion (Setup Page, Digital Input/Output Menu) does

not change the relationship between the input and

the event. An input will still control the input event

state, even if Digital Input Function is set to None.

Actions

Based on a given input (Digital I/O, Event output,

Logic function, etc..) the Action function can cause

other functions to occur. To name a few, set alarms to

off, silencing alarms and reset a tripped limit condi-

tion. Energise

Module Limit

This function allows the user to setup a single out-

put to reflect an energized (safe) or deenergized

(tripped) state for the module. If any configured limit

is tripped (process value exceeds set point or limit in-