Watlow EZ-ZONE

®

RML Module

25

Chapter 2 Install and Wire

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Quencharc Wiring Example

In this example the Quencharc circuit
(Watlow part# 0804-0147-0000) is used to
protect RML internal circuitry from the
counter electromagnetic force from the in-
ductive user load when deenergized. It is
recommended that this or an equivalent
Quencharc be used when connecting induc-
tive loads to RML outputs.

Quencharc

User Load

L_

K_

N

Standard Bus EIA-485 Communications

T-/R-

common

Slot C

T+/R+

98 99

CF CD CE

CZ CX CY

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal

of the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• A 120 Ω termination resistor

may be required across T+/R+

and T-/R-, placed on the last

controller on the network.

• Do not connect more than 16

EZ-ZONE PM controllers on a

network.

• maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus

RMLx-xxxx-x(A)xx

* All models include Standard Bus

communications

Note:

Do not leave a USB to EIA-485 converter connected to Standard Bus with-

out power (i.e., disconnecting the USB end from the computer while leaving

the converter connected on Standard Bus). Disturbance on the Standard

Bus may occur.

Modbus RTU or Standard Bus EIA-485 Communications

T-/R-

common

Slot C

T+/R+

98 99

CC CA CB

CZ CX CY

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal

of the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• A termination resistor may be

required. Place a 120 Ω resistor

across T+/R+ and T-/R- of last

controller on network.

• Only one protocol per port is

available at a time: either Mod-

bus RTU or Standard Bus.

• Do not connect more than 16

EZ-ZONE controllers on a

Standard Bus network.

• Maximum number of EZ-ZONE

controllers on a Modbus net-

work is 247.

• maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus

RMLx-xxxx-x(1)xx

Note:

Do not leave a USB to EIA-485 converter connected to Standard Bus with-

out power (i.e., disconnecting the USB end from the computer while leaving

the converter connected on Standard Bus). Disturbance on the Standard

Bus may occur.

Modbus-IDA

Terminal

EIA/TIA-485

Name

Watlow Terminal

Label

Function

DO

A

CA or CD

T-/R-

D1

B

CB or CE

T+/R+

common

common

CC or CF

common