Digital input/output menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 48
Watlow EZ-ZONE
®
RML Module
•
45
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`dio]
[`Set]
Digital Input/Output Menu
[`dir]
[ dir]
Digital Input/Output (1
to 8)
Direction
Set this function to operate
as an input or output.
[OtPt]
Output (68)
[``in]
Input Voltage (193)
[iCon]
Input Dry Contact
(44)
Output
1850
[offset 30]
0x6A
(106)
1 to 8
1
82
6001
uint
RWES
[`dir]
[ dir]
Digital Input (9)
Direction
Set the input type.
[``in]
Input Voltage (193)
[iCon]
Input Dry Contact
(44)
Dry Con-
tact
2090
[offset 30]
0x6A
(106)
9
1
82
6001
uint
RWES
[``Fn]
[ Fn]
Digital Output (1 to 6)
Function
Select what function will
drive this output.
[`oFF]
Off (62)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[`FUn]
Function Key (1001)
[`lnr]
Linearization (238)
[`LgC]
Logic (239)
[mat]
Math (240)
[tMr]
Timer (244)
[`uAr]
Variable (245)
[m;li]
Module Limit (1696)
[LiM]
Limit (126)
1858
[offset 30]
0x 6A
(106)
1 to 6
5
83
6005
uint
RWES
[``Fi]
[ Fi]
Digital Output (1 to 8)
Function Instance
Set the instance of the
function selected above.
1 to 24
1
1860
[offset 30]
0x6A
(106)
1 to 8
6
84
6006
uint
RWES
[`S2;A]
[ SZ.A]
Digital Output (1 to 8)
Source Zone A
Set the zone of the function
selected above.
0 to 16
0
1872
[offset 30]
0x6A
(106)
1 to 8
0xC (12)
- - - -
6012
uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (1 to 8)
Control
Set the output control type.
This parameter is only
used with PID control, but
can be set anytime.
[`Ftb]
Fixed Time Base (34)
[`utb]
Variable Time Base
(103)
Fixed
Time
Base
1852
[offset 30]
0x6A
(106)
1 to 8
2
85
6002
uint
RWES
[`o;tb]
[ o.tb]
Digital Output (1 to 8)
Time Base
Set the time base for fixed-
time-base control.
[ 0.1 for Fast and Bi-Direc-
tional outputs, 5.0 for Slow
outputs] to 60
1854
[offset 30]
0x6A
(106)
1 to 8
3
86
6003
float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (1 to 8)
Low Power Scale
The power output will nev-
er be less than the value
specified and will represent
the value at which output
scaling begins.
0.0 to 100.0
0.0
1866
[offset 30]
0x6A
(106)
1 to 8
9
87
6009
float
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set