RML Module
•
52
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`iP;1]
[ ip.1]
Linearization (1 to 16)
Input Point 1
Set the value that will be
mapped to output 1.
-1,999.000 to 9,999.000
0.0
8004
[offset 70]
0x86 (134)
1 to 0x10
(16)
8
157
34008
float
RWES
[`oP;1]
[ op.1]
Linearization (1 to 16)
Output Point 1
Set the value that will be
mapped to input 1.
-1,999.000 to 9,999.000
0.0
8024
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x12 (18)
158
34018
float
RWES
[`iP;2]
[ ip.2]
Linearization (1 to 16)
Input Point 2
Set the value that will be
mapped to output 2.
-1,999.000 to 9,999.000
1.0
8006
[offset 70]
0x86 (134)
1 to 0x10
(16)
9
159
34009
float
RWES
[`oP;2]
[ op.2]
Linearization (1 to 16)
Output Point 2
Set the value that will be
mapped to input 2.
-1,999.000 to 9,999.000
1.0
8026
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x13 (19)
160
34019
float
RWES
[`iP;3]
[ ip.3]
Linearization (1 to 16)
Input Point 3
Set the value that will be
mapped to output 3.
-1,999.000 to 9,999.000
2.0
8008
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xA (10)
161
34010
float
RWES
[`oP;3]
[ op.3]
Linearization (1 to 16)
Output Point 3
Set the value that will be
mapped to input 3.
-1,999.000 to 9,999.000
2.0
8028
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x14 (20)
162
34020
float
RWES
[`iP;4]
[ ip.4]
Linearization (1 to 16)
Input Point 4
Set the value that will be
mapped to output 4.
-1,999.000 to 9,999.000
3.0
8010
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xB (11)
163
34011
float
RWES
[`oP;4]
[ op.4]
Linearization (1 to 16)
Output Point 4
Set the value that will be
mapped to input 4.
-1,999.000 to 9,999.000
3.0
8030
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x15 (21)
164
34021
float
RWES
[`iP;5]
[ ip.5]
Linearization (1 to 16)
Input Point 5
Set the value that will be
mapped to output 5.
-1,999.000 to 9,999.000
4.0
8012
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xC (12)
165
34012
float
RWES
[`oP;5]
[ op.5]
Linearization (1 to 16)
Output Point 5
Set the value that will be
mapped to input 5.
-1,999.000 to 9,999.000
4.0
8032
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x16 (22)
166
34022
float
RWES
[`iP;6]
[ ip.6]
Linearization (1 to 16)
Input Point 6
Set the value that will be
mapped to output 6.
-1,999.000 to 9,999.000
5.0
8014
[offset 70]
0x86 (134)
1 to 0x10
(16)
0xD (13)
167
34013
float
RWES
[`oP;6]
[ op.6]
Linearization (1 to 16)
Output Point 6
Set the value that will be
mapped to input 6.
-1,999.000 to 9,999.000
5.0
8034
[offset 70]
0x86 (134)
1 to 0x10
(16)
0x17 (23)
168
34023
float
RWES
[`iP;7]
[ ip.7]
Linearization (1 to 16)
Input Point 7
Set the value that will be
mapped to output 7.
-1,999.000 to 9,999.000
6.0
8016
[offset 70]
0x86 (134)
1 to 0x10
(16)
E (14)
169
34014
float
RWES