beautypg.com

Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 55

background image

Watlow EZ-ZONE

®

RML Module

52

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`iP;1]
[ ip.1]

Linearization (1 to 16)

Input Point 1

Set the value that will be

mapped to output 1.

-1,999.000 to 9,999.000

0.0

8004

[offset 70]

0x86 (134)

1 to 0x10

(16)

8

157

34008

float
RWES

[`oP;1]
[ op.1]

Linearization (1 to 16)

Output Point 1

Set the value that will be

mapped to input 1.

-1,999.000 to 9,999.000

0.0

8024

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x12 (18)

158

34018

float
RWES

[`iP;2]
[ ip.2]

Linearization (1 to 16)

Input Point 2

Set the value that will be

mapped to output 2.

-1,999.000 to 9,999.000

1.0

8006

[offset 70]

0x86 (134)

1 to 0x10

(16)

9

159

34009

float
RWES

[`oP;2]
[ op.2]

Linearization (1 to 16)

Output Point 2

Set the value that will be

mapped to input 2.

-1,999.000 to 9,999.000

1.0

8026

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x13 (19)

160

34019

float
RWES

[`iP;3]
[ ip.3]

Linearization (1 to 16)

Input Point 3

Set the value that will be

mapped to output 3.

-1,999.000 to 9,999.000

2.0

8008

[offset 70]

0x86 (134)

1 to 0x10

(16)

0xA (10)

161

34010

float
RWES

[`oP;3]
[ op.3]

Linearization (1 to 16)

Output Point 3

Set the value that will be

mapped to input 3.

-1,999.000 to 9,999.000

2.0

8028

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x14 (20)

162

34020

float
RWES

[`iP;4]
[ ip.4]

Linearization (1 to 16)

Input Point 4

Set the value that will be

mapped to output 4.

-1,999.000 to 9,999.000

3.0

8010

[offset 70]

0x86 (134)

1 to 0x10

(16)

0xB (11)

163

34011

float
RWES

[`oP;4]
[ op.4]

Linearization (1 to 16)

Output Point 4

Set the value that will be

mapped to input 4.

-1,999.000 to 9,999.000

3.0

8030

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x15 (21)

164

34021

float
RWES

[`iP;5]
[ ip.5]

Linearization (1 to 16)

Input Point 5

Set the value that will be

mapped to output 5.

-1,999.000 to 9,999.000

4.0

8012

[offset 70]

0x86 (134)

1 to 0x10

(16)

0xC (12)

165

34012

float
RWES

[`oP;5]
[ op.5]

Linearization (1 to 16)

Output Point 5

Set the value that will be

mapped to input 5.

-1,999.000 to 9,999.000

4.0

8032

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x16 (22)

166

34022

float
RWES

[`iP;6]
[ ip.6]

Linearization (1 to 16)

Input Point 6

Set the value that will be

mapped to output 6.

-1,999.000 to 9,999.000

5.0

8014

[offset 70]

0x86 (134)

1 to 0x10

(16)

0xD (13)

167

34013

float
RWES

[`oP;6]
[ op.6]

Linearization (1 to 16)

Output Point 6

Set the value that will be

mapped to input 6.

-1,999.000 to 9,999.000

5.0

8034

[offset 70]

0x86 (134)

1 to 0x10

(16)

0x17 (23)

168

34023

float
RWES

[`iP;7]
[ ip.7]

Linearization (1 to 16)

Input Point 7

Set the value that will be

mapped to output 7.

-1,999.000 to 9,999.000

6.0

8016

[offset 70]

0x86 (134)

1 to 0x10

(16)

E (14)

169

34014

float
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set