beautypg.com

Math menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 42

background image

Watlow EZ-ZONE

®

RML Module

39

Chapter 3 Operations Page

RM Limit Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

No Dis-

play

Logic (1 to 16)

Output Error

View reported cause for

logic error

None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)

4700
[offset 80]

0x7F

(127)

1 to 0x10

(16)

0x24 (36)

- - - -

27036

uint

R

[MAt]
[oPEr]
Math Menu

[`Su;A]
[ Su.A]

Math (1 to 16)

Source Value A

View the value of Source

A.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

3540
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x10 (16)

- - - -

25016

float
RWES

[`Su;b]
[ Su.b]

Math (1 to 16)

Source Value B

View the value of Source

B.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

3542
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x11 (17)

- - - -

25017

float
RWES

[`Su;C]
[ Su.C]

Math (1 to 16)

Source Value C

View the value of Source

C.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

3544
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x12 (18)

- - - -

25018

float
RWES

[`Su;d]
[ Su.d]

Math (1 to 16)

Source Value D

View the value of Source

D.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

3546
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x13 (19)

- - - -

25019

float
RWES

[`Su;E]
[ Su.E]

Math (1 to 16)

Source Value E

View the value of Source

E.

[`off]

Off (62)

[``on]

On (63)

3548
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x14 (20)

- - - -

25020

uint
RWES

[oFSt]
[oFSt]

Math (1 to 16)

Offset

Set an offset to be applied

to this function's output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0

3554
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x17 (23)

- - - -

25023

float
RWES

[``o;u]
[ o.v]

Math (1 to 16)

Output Value

View the value of this

function's output.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

3552
[offset 70]

0x7D

(125)

1 to 0x10

(16)

0x16 (22)

- - - -

25022

float
RWES

Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set