beautypg.com

Chapter 7: appendix, Modbus - programmable memory blocks, Bus programmable memory blocks – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 114: Modbus programmable, Memory blocks

background image

Watlow EZ-ZONE

®

RML Module

111

Appendix

7

Chapter 7: Appendix

Modbus - Programmable Memory Blocks

The Modbus assembly contains 40 pointers to the parameters of your choosing starting at Modbus register

40 (shown on the following page). The pointers are 32-bits long so are stored in two sequential registers. As

an example, if we want to move an alias to the analog input of the RML (register 410) into register 40, we

perform a multiple write command (0x10 function) of 410 into register 40 and 411 into register 41 as a single

multi-write command.
Once the parameters of choice have been defined and written to the pointer registers, the working registers

200 to 279 then represent those parameters. Therefore, as in the example above, if 410 is in register 40, 411

in register 41, register 200 & 201 contains the 32-bit floating point result for analog input 1.

The screen shot above was taken from a program that can be found on the Watlow Support Tools DVD

(shipped with the product) as well as on the Watlow website. On the DVD, it can be found under "Utility

Tools" and is identified as "Modbus RTU Diagnostic Program for EZ-ZONE PM, RM and ST". A similar pro-

gram can be found here as well for a connection utilizing Ethernet TCP.
If it is easier to go to the web to acquire this software click on the link below and type "modbus" in the

search field where both versions can be found with the same name.

http://www.watlow.com/literature/soft-

ware.cfm