beautypg.com

Action menu, Limit menu, Action menu limit menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 36

background image

Watlow EZ-ZONE

®

RML Module

33

Chapter 3 Operations Page

RM Limit Module

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

No Dis-

play

Digital Input (1 to 6 and 9)

Source Error

View the state of this out-

put.

None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Calibration Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)

None

1878

[offset 30]

0x6A (106)

1 to 9

0x0F (15)

- - - -

6015

uint

R

No Dis-

play

Digital Output (1 to 8)

Output State

View the state of this out-

put.

Off (62)
On (63)

- - - -

1862

[offset 30]

0x6A (106)

1 to 8

7

- - - -

6007

uint

R

[`ACt]
[oPEr]
Action Menu

[`Ei;S]
[ Ei.S]

Action (1 to 16)

Event Input Status

View this input state.

[`off]

Off (62)

[``on]

On (63)

2218
[offset 20]

0x6E (110)

1 to 0x10

(16)

5

140

10005

uint
R

No Dis-

play

Function Key (1)

Function Key State

View current state of func-

tion key 1.

Off (62)
On (63)

- - - -

- - - -

- - - -

- - - -

3024

uint

R

No Dis-

play

Function Key (2)

Function Key State

View current state of func-

tion key 2..

Off (62)
On (63)

- - - -

- - - -

- - - -

- - - -

3030

uint

R

[LiM]
[oPEr]
Limit Menu

[`LL;S]
[ LL.S]

Limit (1 to 12)

Low Set Point

Set the low process value

that will trigger the limit.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

1494
[offset 30]

0x70 (112)

1 to 0xC

(12)

3

38

12003

float
RWES

[`Lh;S]
[ Lh.S]

Limit (1 to 12)

High Set Point

Set the high process value

that will trigger the limit.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

0.0°F or

units

-18.0°C

1496
[offset 30]

0x70 (112)

1 to 0xC

(12)

4

39

12004

float
RWES

[`l;Cr]

[L.Cr]

Limit (1 to 12)

Clear Request

Clear limit once limit con-

dition is cleared.

Clear (129)

Ignore (204)

Ignore

- - - -

- - - -

- - - -

12014

uint

R

[`l;st]

[L.St]

Limit (1 to 12)

Status

Reflects whether or not

the limit is in a safe or

failed mode..

Fail (32)

Safe (1667)

- - - -

1514
[offset 30]

0x70 (112)

1 to 0xC

(12)

0x0D (13)

- - - -

12013

uint

R

No Dis-

play

Limit (1 to 12)

State

Current state of limit.

Off (62)

None (61)

Limit High (51)

Limit Low (52)

Error (225)

- - - -

1500

[offset 30]

0x70 (112)

1 to 0xC

(12)

6

- - - -

12006

uint

R

Note: Some values will be rounded off to fit in the four-character display . Full values
can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set