Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 53
![background image](/manuals/359088/53/background.png)
Watlow EZ-ZONE
®
RML Module
•
50
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`A;Sd]
[ A.Sd]
Alarm (1 to 16)
Sides
Select which side or sides
will trigger this alarm.
[both]
Both (13)
[high]
High (37)
[LoW]
Low (53)
Both
2536
[offset 60]
0x6D
(109)
1 to 0x10
(16)
4
26
9004
uint
RWES
[`A;Lo]
[ A.Lo]
Alarm (1 to 16)
Low Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger a
low alarm.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
32.0°F
or units
0.0°C
- - - -
- - - -
- - - -
- - - -
- - - -
[`A;hi]
[ A.hi]
Alarm (1 to 16)
High Set Point
If Alarm Type (Setup
Page, Alarm Menu) is
set to:
process - set the process
value that will trigger a
high alarm.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
300.0°F
or units
150.0°C
- - - -
- - - -
- - - -
- - - -
- - - -
[`A;LA]
[ A.LA]
Alarm (1 to 16)
Latching
Turn alarm latching on or
off. A latched alarm has to
be turned off by the user.
[nLAt]
Non-Latching (60)
[`LAt]
Latching (49)
Non-
Latching
2542
[offset 60]
0x6D
(109)
1 to 0x10
(16)
7
27
9007
uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 16)
Blocking
Select when an alarm will
be blocked. After startup
and/or after the set point
changes, the alarm will be
blocked until the process
value enters the normal
range.
[`oFF]
Off (62)
[`Str]
Startup (88)
[StPt]
Set Point (85)
[both]
Both (13)
Off
2544
[offset 60]
0x6D
(109)
1 to 0x10
(16)
8
28
9008
uint
RWES
[`A;Si]
[ A.Si]
Alarm (1 to 16)
Silencing
Turn alarm silencing on to
allow the user to disable
this alarm.
[`oFF]
Off (62)
[``on]
On (63)
Off
2540
[offset 60]
0x6D
(109)
1 to 0x10
(16)
6
29
9006
uint
RWES
[A;dSP]
[A.dSP]
Alarm (1 to 16)
Display
Display an alarm message
when an alarm is active.
[`oFF]
Off (62)
[``on]
On (63)
On
2560
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x10 (16)
30
9016
uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 16)
Delay
Set the span of time that
the alarm will be delayed
after the process value ex-
ceeds the alarm set point.
0 to 9,999 seconds
0
2570
[offset 60]
0x6D
(109)
1 to 0x10
(16)
0x15 (21)
31
9021
uint
RWES
[A;Clr]
[ A.hi]
Alarm (1 to 16)
Clear Request
Write to this register to
clear an alarm
Clear
Ignore
Ignore
- - - -
- - - -
- - - -
- - - -
- - - -
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set