Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 59
Watlow EZ-ZONE
®
RML Module
•
56
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[SFn;B]
[SFn.b]
Timer (1 to 16)
Source Function B
Set the type of function
that will be used to reset
a retentive timer (reset
signal).
[nonE]
None (61)
[ALM]
Alarm Reset (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[SoF;1]
Special Function Out-
put 1 (1532)
[SoF;2]
Special Function Out-
put 2 (1533)
[SoF;3]
Special Function Out-
put 3 (1534)
[SoF;4]
Special Function Out-
put 4 (1535)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
7192
[offset 50]
0x83 (131)
1 to 16
2
- - - -
31002
uint
RWES
[`Si;B]
[ Si.b]
Timer (1 to 16)
Source Instance B
Set the instance of the
function selected above.
1 to 250
1
7196
[offset 50]
0x83 (131)
1 to 16
4
- - - -
31004
uint
RWES
[`S2;B]
[ SZ.b]
Timer (1 to 16)
Source Zone B
Set the zone of the function
selected above.
0 to 16
0
7200
[offset 50]
0x83 (131)
1 to 16
6
- - - -
31006
uint
RWES
[sas;b]
[SAS.b]
Timer (1 to 16)
Source Active State B
Set what state will be read
as on.
[high]
High (37)
[LoW]
Low (53)
High
7212
[offset 50]
0x83 (131)
1 to 4
0xC (12)
- - - -
31012
uint
RWES
[``ti]
[ ti]
Timer (1 to 16)
Time
Set the time span that will
be measured.
0 to 9,999.000
1.0
7214
[offset 50]
0x83 (131)
1 to 16
0xD (13)
224
31013
float
RWES
[`LEu]
[ LEv]
Timer (1 to 16)
Active Level
Set which output state will
indicate on.
[high]
High (37)
[LoW]
Low (53)
High
7216
[offset 50]
0x83 (131)
1 to 16
0xE (14)
- - - -
31014
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set