Action menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual
Page 49
Watlow EZ-ZONE
®
RML Module
•
46
•
Chapter 4 Setup Page
RM Limit Module
•
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`o;hi]
[ o.hi]
Digital Output (1 to 8)
High Power Scale
The power output will
never be greater than the
value specified and will
represent the value at
which output scaling stops.
0.0 to 100.0
100.0
1868
[offset 30]
0x6A
(106)
1 to 8
0xA (10)
88
6010
float
RWES
[`ACt]
[`SEt]
Action Menu
[``Fn]
[ Fn]
Action (1 to 16)
Function
Set the action that will be
triggered by this function.
[nonE]
None (61)
[USr;r]
User Settings Re-
store (227)
[ALM]
Alarm Reset (6)
[`SiL]
Silence Alarms (108)
[`AoF]
Control Loop Off and
Alarms to Non-alarm State
(220)
[`F;AL]
Force Alarm to Occur
(218)
None
2214
[offset 20]
0x6E
(110)
1 to 0x10
(16)
3
138
10003
uint
RWES
[``Fi]
[ Fi]
Action (1 to 16)
Function Instance
Set the instance of the
function selected above.
0 to 25
0
2216
[offset 20]
0x6E
(110)
1 to 0x10
(16)
4
139
10004
uint
RWES
[SFn;A]
[SFn.A]
Action (1 to 16)
Source Function A
Set the event or function
that will trigger the action.
[nonE]
None (61)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[LiM]
Limit (126)
[`LgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245)
None
2220
[offset 20]
0x6E
(110)
1 to 0x10
(16)
6
- - - -
10006
uint
RWES
Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EEPROM
S:
User
Set