beautypg.com

Action menu – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 49

background image

Watlow EZ-ZONE

®

RML Module

46

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`o;hi]
[ o.hi]

Digital Output (1 to 8)

High Power Scale

The power output will

never be greater than the

value specified and will

represent the value at

which output scaling stops.

0.0 to 100.0

100.0

1868
[offset 30]

0x6A

(106)

1 to 8

0xA (10)

88

6010

float
RWES

[`ACt]
[`SEt]
Action Menu

[``Fn]
[ Fn]

Action (1 to 16)

Function

Set the action that will be

triggered by this function.

[nonE]

None (61)

[USr;r]

User Settings Re-

store (227)

[ALM]

Alarm Reset (6)

[`SiL]

Silence Alarms (108)

[`AoF]

Control Loop Off and

Alarms to Non-alarm State

(220)

[`F;AL]

Force Alarm to Occur

(218)

None

2214
[offset 20]

0x6E

(110)

1 to 0x10

(16)

3

138

10003

uint
RWES

[``Fi]
[ Fi]

Action (1 to 16)

Function Instance

Set the instance of the

function selected above.

0 to 25

0

2216
[offset 20]

0x6E

(110)

1 to 0x10

(16)

4

139

10004

uint
RWES

[SFn;A]
[SFn.A]

Action (1 to 16)

Source Function A

Set the event or function

that will trigger the action.

[nonE]

None (61)

[ALM]

Alarm (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[LiM]

Limit (126)

[`LgC]

Logic (239)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

2220
[offset 20]

0x6E

(110)

1 to 0x10

(16)

6

- - - -

10006

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set