IAI America RCM-GW-PR User Manual
Page 32
26
PfofiBus Gateway
a. Detail connection diagram
Details of SIO link connection are illustrated below. Controller link cables are available as options, but
the customer must provide the communication trunk.
b. Producing a communication trunk
[1] Strip the sheath of a double shielded twisted-pair cable by
approx. 15 to 20 mm.
[2] Twist the shield wires and solder them onto the vinyl
wires of AWG22 or equivalent.
[3] Place a cable protection tube over the cable.
[4] Insert the core wires, without stripping them, into the
cable insertion holes in the connector (SDA, SDB,
GND, FG).
[5] With the cable inserted in the press-fit cable housing, apply
pressure from above to pressure-weld the core wires.
[6] Heat-treat the cable protection tube.
e-CON connector pin numbers
Always insert a terminal resistor (220
Ω, 1/4 W) at the end of the communication trunk
(between pins 1 and 2 of the e-CON connector).
Gateway Unit
Double shielded
twisted-pair cable
Recommended cable:
HK-SB/20276 X L
2P X AWG22 by Taiyo
Electric Wire & Cable
SIO communication trunk
4-way junction (5-1473574-4 by AMP)
e-CON connector (4-1473562-4 by AMP)
Housing color: Green
Controller link cable
Yellow
Orange
Blue
Yellow
Orange
Blue
e-CON connector (3-1473562-4 by AMP)
Housing color: Orange
Unit 1
Unit 2
Locking tab
e-CON connector
Apply pressure.
Cable tube
Double shielded twisted-pair shielded
Locking tab
Vinyl wire
(AWG22)
Solder
Shield
wire