13.2. Auxiliary functions
The following additional functions can be configured and parameterized via the communications software:
Function
Description
DIR.ACTUATOR
Assignment of the aeration status of the actuator chamber to the actual position
SPLITRANGE
Signal split range; input signal as a % for which the valve runs through the entire
stroke range.
X.LIMIT
Limit the mechanical stroke range
X.TIME
Limit the control speed
X.CONTROL
Parameterize the position controller
SAFE POSITION
Input the safety position
SIGNAL ERROR
Configuration of signal level fault detection
BINARY INPUT
Activation of the binary input
OUTPUT
Configuration of the outputs (only with auxiliary board for analogue feedback signal
or binary outputs)
Table 32:
Auxiliary functions
The operating instructions for the communications software describe in detail the individual functions, as
well as parameterization and configuration.
and are also available on CD which
can be ordered by quoting identification number 804625.