Electrical installation with cable gland, Designation of the screw-type terminals, Connection of the positioner type 8694 – Burkert Type 8694 User Manual
Page 46
46
Electricalinstallation24VDC
10.3. Electrical installation with cable gland
DANGER!
Risk of electric shock!
• Before reaching into the device or the equipment,
switch off the power supply and secure to prevent reactivation!
• Observe applicable accident prevention and safety regulations for electrical equipment!
10.3.1. Designation of the screw-type terminals
1
2
16)
3
16)
4
5
6
7
Figure 29:
Connection of screw-type terminals
10.3.2. Connection of the positioner Type 8694
→
The screw-type terminals can be accessed by unscrewing the body casing (stainless steel).
→
Push the cables through the cable gland.
→
Connect the positioner according to the following tables:
Input signals from the control centre (e.g. PLC)
Terminal Configuration
External circuit
4
5
Set-point value +
Set-point value GND
4
5
GND
+ (0/4 ... 20 mA)
1
Binary input +
1
+
0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
with reference to terminal 7 (GND)
Table 18:
Assignment of screw-type terminals - input signals of the control center - cable gland
16)
Option only