10.3. Electrical installation with cable gland

DANGER!

Risk of electric shock!

• Before reaching into the device or the equipment,

switch off the power supply and secure to prevent reactivation!

• Observe applicable accident prevention and safety regulations for electrical equipment!

10.3.1. Designation of the screw-type terminals

1

2

16)

3

16)

4

5

6

7

Figure 29:

Connection of screw-type terminals

10.3.2. Connection of the positioner Type 8694

The screw-type terminals can be accessed by unscrewing the body casing (stainless steel).

Push the cables through the cable gland.

Connect the positioner according to the following tables:

Input signals from the control centre (e.g. PLC)

Terminal Configuration

External circuit

4

5

Set-point value +

Set-point value GND

4

5

GND

+ (0/4 ... 20 mA)

1

Binary input +

1

+

0 ... 5 V (log. 0)
10 ... 30 V (log. 1)

with reference to terminal 7 (GND)

Table 18:

Assignment of screw-type terminals - input signals of the control center - cable gland

16)

Option only

English

Type 8694