Burkert Type 8694 User Manual
Page 56
56
Operationandfunction
13.1.1. DIR.CMD -
Effective direction of the positioner set-point value
You can use this function to adjust the effective direction between the input signal (INPUT) and the nominal
position of the actuator.
Factory setting: DIP switch set to OFF (ascending)
DIP Switches Position
Function
1
ON
Reversal of the effective direction of the set-point value (
DIR.CMD)
(set-point value 20 – 4 mA corresponds to position 0 – 100 %), fall
OFF
Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position 0 – 100 %),
rise
Table 28:
DIP switch 1
The effective direction (
DIR.CMD) can only be changed via DIP switch 1 in the positioner.
Nominal position
Input signal
(
INPUT)
rise
fall
Figure 39:
DIR.CMD graph
English
Type 8694
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0330 (2 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (5 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0311 (2 pages)
- Type 0312 (6 pages)
- Type 6518 (57 pages)
- Type 6519 (3 pages)