Operationandfunction

13.

OPERATION AND FUNCTION

The positioner type 8694 has different basic and additional functions which can be configured and parameterized
via the DIP switches or the communications software.

13.1. Basic functions

The following basic functions can be activated via the DIP switches (

CUTOFF and CHARACT) or changed

(

DIR.CMD).

Function

Description

DIP Switches OFF

ON

DIR.CMD

Effective direction between input
signal and set-point position

1

rise

fall

CUTOFF

Sealing function for position
controller

2

Sealing function off

Sealing function on

CHARACT

Selection of the Transfer Charac-
teristic between Input Signal and
Stroke (Correction Characteristic)

3

Linear characteristic Correction

characteristic

Table 26:

Basic functions of DIP switches

The following basic function can be changed via the communications software only.

Function

Description

Factory setting

INPUT

Entry of the standard signal input
for the set-point value

4 ... 20 mA

Table 27:

Basic function of communications software

The

INPUT, CUTOFF and CHARACT functions can be parameterized via the communications software.

The operating instructions for the communications software describe in detail the individual functions, as
well as parameterization and configuration.

These instructions can be found on the Internet at

www.burkert.com

and are also available on CD which

can be ordered by quoting identification number 804625.

English

Type 8694