Operationandfunction
13.
OPERATION AND FUNCTION
The positioner type 8694 has different basic and additional functions which can be configured and parameterized
via the DIP switches or the communications software.
13.1. Basic functions
The following basic functions can be activated via the DIP switches (
CUTOFF and CHARACT) or changed
(
DIR.CMD).
Function
Description
DIP Switches OFF
ON
DIR.CMD
Effective direction between input
signal and set-point position
1
rise
fall
CUTOFF
Sealing function for position
controller
2
Sealing function off
Sealing function on
CHARACT
Selection of the Transfer Charac-
teristic between Input Signal and
Stroke (Correction Characteristic)
3
Linear characteristic Correction
characteristic
Table 26:
Basic functions of DIP switches
The following basic function can be changed via the communications software only.
Function
Description
Factory setting
INPUT
Entry of the standard signal input
for the set-point value
4 ... 20 mA
Table 27:
Basic function of communications software
The
INPUT, CUTOFF and CHARACT functions can be parameterized via the communications software.
The operating instructions for the communications software describe in detail the individual functions, as
well as parameterization and configuration.
and are also available on CD which
can be ordered by quoting identification number 804625.
English
Type 8694