Burkert Type 8694 User Manual
Page 47
47
Electricalinstallation24VDC
Output signals to the control center (e.g. PLC; for analog output option only)
Terminal Configuration
External circuit
2
3
Analogue position feedback +
Analogue position feedback GND
2
3
GND
+ (0/4 ... 20 mA)
Table 19:
Assignment of screw-type terminals - output signals to the control center - cable gland
Electrical supply voltage
Terminal Configuration
External circuit
6
7
Supply voltage +
Supply voltage GND
6
7
24 V DC ± 10 %
max. residual ripple 10 %
Table 20:
Assignment of screw-type terminals - Supply voltage - cable gland
Seal
body casing
Body casing
Figure 30:
Position of the seal in the body casing
→
Check that the seal is correctly positioned in the body casing.
NOTE!
Damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable size or dummy plugs used (approx. 1.5 Nm).
• Screw the body casing in all the way.
→
Tighten union nut on the cable gland (torque approx. 1.5 Nm).
→
Close the device (assembly tool: 674077
17)
).
When the power supply is applied, the positioner is operating.
→
Make the required basic settings and actuate the automatic adjustment of the positioner, as described in the
chapter entitled “12. Start-up”.
17)
The assembly tool (674077) is available from your Bürkert sales office.
English
Type 8694