Tpi alarms – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 61

57
Displayed Alarm /
Warning
Device
Description
Recommended Actions
Line Not Learned
Line
Specified line not learned.
Complete learn process, if any learn alarms occur follow the
proper procedure. Refer to “LS500 Auto Learn Line Leak Detection
Installation & User’s Guide” FFS 000-2145 for more information.
Line Program Error
Detected
Line
An error has been detected in the
programming of the specified line.
Verify programming of line under the setup menu.
Line Pump Request
Ignored
Engineering The line has called for the pump
to be turned on but another
application is currently using the
STP
Verify that other applications are operating properly. Contact Franklin
Fueling Systems’ Technical Services Dept. for support.
Marginal Pass of Gross
Leak Test
Line
The last passed gross test
detected a leak just under the
3 gph threshold.
Verify there is no sign of leaks within any of the sumps. Run
additional tests. Refer to “LS500 Auto Learn Line Leak Detection
Installation & User’s Guide” FFS 000-2145 for more information.
Monthly Leak Test Failed
Line
The Console has detected a line
leak greater than 0.2 gph.
Inspect all sumps for product. Refer to “LS500 Auto Learn Line
Leak Detection Installation & User’s Guide” FFS 000-2145 for more
information.
Not Enabled
Line
Line testing has not been enabled. Verify no other alarm is present then enter the line control menu and
enable the line testing feature.
Precision Leak Test Failed
Line
0.1 GPH Line leak test failed.
Follow site policy on line leak procedures.
Pressure Transducer Fail
Line
The transducer is not being
detected by the console.
Inspect the wiring to the specified transducer and the channel it
terminates at. Refer to “LS500 Auto Learn Line Leak Detection
Installation & User’s Guide” FFS 000-2145 for more information.
Sudden Pressure Loss
Line
During a 45 minute quite period
the pressure was seen to drop by
a 2 times the learned 3 gph slope.
Inspect all sumps for product. Refer to “LS500 Auto Learn Line
Leak Detection Installation & User’s Guide” FFS 000-2145 for more
information.
TPI Alarms
Displayed Alarm /
Warning
Device
Description
Recommended Actions
Capacitor Failing
TPI
The STP controller is reporting a
capacitor failure.
Refer to the applicable Smart controller Installation guide for details.
Clogged Intake
TPI
The STP controller has reported
a dry run condition but the
associated tank shows a product
level above the intake.
Ensure proper programming of the TPI and calibration of the Smart
Controller. If correct, check for an obstruction on the PMA.
Communication Failure
TPI
Communication from the TPI to
the STP controller has failed. The
Console is seeing the controller
but the controller is not responding
to commands.
Verify all wiring connections. Call FFS Technical Services Department
for support.
Controller Type Error
TPI
The programmed controller type
does not match what the console
is detecting.
Verify proper programming of the TPI as well as the Smart controller
type and address.
Dry Tank
TPI
The STP Controller has reported
a dry run condition and the
tank level is at or below the
programmed intake.
Ensure proper programming of the TPI and calibration of the Smart
Controller. If correct, add fuel.
Extended Run
TPI
The STP controller is reporting an
extended run condition.
Refer to the applicable Smart Controller Installation guide for details.
Hardware Fault
TPI
The STP controller is reporting
is reporting a hardware fault
condition.
High Temperature
TPI
The STP controller is reporting a
high temperature condition.
Locked Rotor
TPI
The STP controller is reporting a
locked rotor rating.
Not Calibrated
TPI
The STP controller is reporting
that it has not been calibrated.
Open Circuit
TPI
The STP controller is reporting an
open circuit condition.
Over Speed
TPI
The STP controller is reporting an
over speed condition.
Refer to the applicable Smart Controller Installation guide for details
Over Voltage
TPI
The STP controller is reporting an
over voltage condition.