Programming Modules

The Fuel Management System is composed of a custom set of modules. Each module maintains individual characteristics.

Parameters must be set to match the site configuration. The programming table below will assist in this setup.
Remote Data Transfer Units (DTU’s)

Remote Data Transfer Units (DTU’s) are used in California for the purpose of relaying information from various sensors

mounted in dispensers to the FFS console.

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

Remote Data Transfer Units

Network ID

(1)

The I.D. of the network.

#

Number of units

(0)

The number of DTUs in the field.

1-16

DTU 1

Unit ID

(0)

Insert the Serial number of the first DTU.

abc#

For Further DIM or DTU Setup information, refer to the Web Browser Interface Section.
IO Modules

The Low Voltage Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs

that can range from 0 to 240 volts. In addition to the AC / DC inputs, the IO module also includes four 4-20mA signal outputs.

Group Name

Parameter

Name

Parameter

Default

Description

Parameter Input

IO Modules

Module #

Inputs

Channels

(0)

The number of A/C or D/C inputs physically wired to the gauge.

0-8

Channel #

Name

(Input 1)

Descriptive name used to identify the input.

abc#

Enabled

(Yes)

Enables the input.

Yes / No

Active State

(High)

High will activate channel when high voltage is present.

Low will activate channel with no voltage present.

High / Low

Action

(None)

Create an alarm or event timestamp .

None

Alarm

Event

Outputs

Channels

(0)

Number of 4-20mA channels in use per module.

0-4

Channel #

Name

(output 1)

Descriptive name used to identify the output

abc

Enable

(Yes)

Yes if the channel is in use

Yes / No

AC Input Modules

The AC Input Module is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can

be used for dispenser hook isolation, vapor processor input, or as generic AC inputs.

Group Name

Parameter Default

Parameter

Default

Description

Parameter

Input

AC Input Modules

Number Gasoline Hooks per

Dispenser

(0)

Including diesel. This is for reference only

except on VRM applications.

0-8

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(AC Input 1)

Given name of channel.

abc#

Enabled

(Yes)

Yes if channel is used.

Yes / No

Active State

(High)

High will activate channel when high voltage

is present. Low will activate channel with no

voltage present.

High / Low

Action Setup

None

Create an alarm or event timestamp

None, Alarm,

Event