Programming modules – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 25

21
Programming Modules
The Fuel Management System is composed of a custom set of modules. Each module maintains individual characteristics.
Parameters must be set to match the site configuration. The programming table below will assist in this setup.
Remote Data Transfer Units (DTU’s)
Remote Data Transfer Units (DTU’s) are used in California for the purpose of relaying information from various sensors
mounted in dispensers to the FFS console.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Remote Data Transfer Units
Network ID
(1)
The I.D. of the network.
#
Number of units
(0)
The number of DTUs in the field.
1-16
DTU 1
Unit ID
(0)
Insert the Serial number of the first DTU.
abc#
For Further DIM or DTU Setup information, refer to the Web Browser Interface Section.
IO Modules
The Low Voltage Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs
that can range from 0 to 240 volts. In addition to the AC / DC inputs, the IO module also includes four 4-20mA signal outputs.
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
IO Modules
Module #
Inputs
Channels
(0)
The number of A/C or D/C inputs physically wired to the gauge.
0-8
Channel #
Name
(Input 1)
Descriptive name used to identify the input.
abc#
Enabled
(Yes)
Enables the input.
Yes / No
Active State
(High)
High will activate channel when high voltage is present.
Low will activate channel with no voltage present.
High / Low
Action
(None)
Create an alarm or event timestamp .
None
Alarm
Event
Outputs
Channels
(0)
Number of 4-20mA channels in use per module.
0-4
Channel #
Name
(output 1)
Descriptive name used to identify the output
abc
Enable
(Yes)
Yes if the channel is in use
Yes / No
AC Input Modules
The AC Input Module is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can
be used for dispenser hook isolation, vapor processor input, or as generic AC inputs.
Group Name
Parameter Default
Parameter
Default
Description
Parameter
Input
AC Input Modules
Number Gasoline Hooks per
Dispenser
(0)
Including diesel. This is for reference only
except on VRM applications.
0-8
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(AC Input 1)
Given name of channel.
abc#
Enabled
(Yes)
Yes if channel is used.
Yes / No
Active State
(High)
High will activate channel when high voltage
is present. Low will activate channel with no
voltage present.
High / Low
Action Setup
None
Create an alarm or event timestamp
None, Alarm,
Event