Probe Modules

The Probe Module gather data from probes, vapor flow meter and TS-DMS sensors. This information is processed by

the Controller Module for use in inventory, reconciliation, V/L Ratio calculation, TS-DMS sensor alarms and to provide

information for reports.

If a DTU is being used there will be an option for a “virtual module” labeled Remote Module. The Remote Module gathers

information from the vapor flow meter when a DTU is used. (see DTU Programming for further details on page 31 in this manual.)

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

Probe Modules

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(Probe 1)

Given Name of Probe.

abc#

Type

(TS-LL2)

Type of device connected.

TS-VFM

TS-LL2

TS-DMS

Remote Module 2

Channels

(6)

Number of DTU devices in use

0-12

Channel 1 (TS-DTU 1) Name

DTU 1-VFM 1

Unique name given to channel

abc#

Type

TS-VFM

Type of device connected.

TS-VFM

2-Wire Sensor Modules

The 2-Wire Sensor Module is designed to accept 12 sensor inputs per module, and the system as a whole can accept a

total of 36 sensors (3 modules with 12 inputs each). The module only supports standard sensors, and does not accept

inputs from 3-wire BriteSensors

®

.

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

2-Wire Sensor Modules

Module #

Channels

(0)

Number of channels in use per module.

0-12

Channel #

Name

(2-Wire Sensor

1)

Given name of channel.

abc#

Monthly Compliance

(Yes)

Select Yes if this sensor is to appear on the

Compliance page and in the Regulatory report

Yes/No

3-Wire Sensor Modules

The 3-Wire Sensor Module is designed to accept 8 sensor inputs per module, and the system as a whole can accept a

total of 24 sensors (3 modules with 8 inputs each). The 3WSNS can support standard sensors and BriteSensors

®

.

Note: When the number of 3-wire sensor channels is selected, the system will automatically detect the connected

sensors and populate the setup with the detected types.

Group Name

Parameter

Name

Parameter

Default

Description

Parameter Input

3-Wire Sensor Modules

Module #

Channels

(0)

Number of channels in use

per module.

0-12

Channel #

Name

(3-Wire Sensor 1) Given name of channel.

abc#

Type

(Interstitial

(EIS) or 2-Wire

Sensor)

The type of sensor

connected to the channel.

After the Channels are

entered this will fill in

automatically.

Unknown,

Interstitial (EIS) or 2-Wire Sensor

Discriminating Interstitial Sensor (DIS)

Discriminating Dispenser Sump Sensor (DDS)

Discriminating Turbine Sump Sensor (DTS)

Monitoring Well Sensor (MWS)

Hydrostatic Interstitial Brine Reservoir Sensor (HIS)

Discriminating Monitoring Well Vapor Sensor (DVS)

Monthly

Compliance

(Yes)

Select Yes if this sensor

is to appear on the

Compliance page and in

the Regulatory report

Yes / No