Probe Modules
The Probe Module gather data from probes, vapor flow meter and TS-DMS sensors. This information is processed by
the Controller Module for use in inventory, reconciliation, V/L Ratio calculation, TS-DMS sensor alarms and to provide
information for reports.
If a DTU is being used there will be an option for a “virtual module” labeled Remote Module. The Remote Module gathers
information from the vapor flow meter when a DTU is used. (see DTU Programming for further details on page 31 in this manual.)
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Probe Modules
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(Probe 1)
Given Name of Probe.
abc#
Type
(TS-LL2)
Type of device connected.
TS-VFM
TS-LL2
TS-DMS
Remote Module 2
Channels
(6)
Number of DTU devices in use
0-12
Channel 1 (TS-DTU 1) Name
DTU 1-VFM 1
Unique name given to channel
abc#
Type
TS-VFM
Type of device connected.
TS-VFM
2-Wire Sensor Modules
The 2-Wire Sensor Module is designed to accept 12 sensor inputs per module, and the system as a whole can accept a
total of 36 sensors (3 modules with 12 inputs each). The module only supports standard sensors, and does not accept
inputs from 3-wire BriteSensors
®
.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
2-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use per module.
0-12
Channel #
Name
(2-Wire Sensor
1)
Given name of channel.
abc#
Monthly Compliance
(Yes)
Select Yes if this sensor is to appear on the
Compliance page and in the Regulatory report
Yes/No
3-Wire Sensor Modules
The 3-Wire Sensor Module is designed to accept 8 sensor inputs per module, and the system as a whole can accept a
total of 24 sensors (3 modules with 8 inputs each). The 3WSNS can support standard sensors and BriteSensors
®
.
Note: When the number of 3-wire sensor channels is selected, the system will automatically detect the connected
sensors and populate the setup with the detected types.
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
3-Wire Sensor Modules
Module #
Channels
(0)
Number of channels in use
per module.
0-12
Channel #
Name
(3-Wire Sensor 1) Given name of channel.
abc#
Type
(Interstitial
(EIS) or 2-Wire
Sensor)
The type of sensor
connected to the channel.
After the Channels are
entered this will fill in
automatically.
Unknown,
Interstitial (EIS) or 2-Wire Sensor
Discriminating Interstitial Sensor (DIS)
Discriminating Dispenser Sump Sensor (DDS)
Discriminating Turbine Sump Sensor (DTS)
Monitoring Well Sensor (MWS)
Hydrostatic Interstitial Brine Reservoir Sensor (HIS)
Discriminating Monitoring Well Vapor Sensor (DVS)
Monthly
Compliance
(Yes)
Select Yes if this sensor
is to appear on the
Compliance page and in
the Regulatory report
Yes / No