Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 58

54
Displayed Alarm /
Warning
Device
Description
Recommended Actions
Manifold low low product
volume
Tank
The specified manifold has
reached the programmed Low
Low Product Volume
Check product volume and compare to the programmed Low Low
Volume alarm Limit in the setup menu. Acquire an accurate product
volume and compare to the ATG. If levels differ, verify programming is
correct. If alarm persists, contact FFS Technical Services for support.
Manifold Leak Detected
Tank
A leak in the specified manifolded
tanks has been detected via a
SCALD test. Suspect possible
leak.
Review Tank Leak Test History and programming. Refer to Section
5: Misc/Tank Leak Tests – Type and Frequency for instructions on
manually starting line leak tests.
Manifold Theft Detected
Tank
The specified manifold has entered
Sentinel Mode and detects product
leaving the tank that exceeds the
programmed theft limits.
Verify programming and accurate level / volume readings.
Modem Error
None
Indicates that a modem
malfunction has occurred.
Try to recycle power on the console. Verify modem programming. If
the alarm does not clear, contact Franklin Fueling Systems’ Technical
Services Dept. for support on this issue.
Net error
Tank
Product net levels exceed tank
diameter
Verify tank, product offset and probe programming
No data available
System
A communication issue has
occurred between the probe and
the console
Check for proper probe programming at the console and inspect
wire connections at the probe. If the problem persists, contact FFS
Technical Services for support.
No probe detected
Tank
The Console is not receiving any
communication from the probe.
Check for proper probe programming at the console and inspect
wire connections at the probe. If the problem persists, contact FFS
Technical Services for support.
Probe synchronization
error
Tank
Communication between the
probe and the Console is either
incomplete or ill timed.
Check for proper probe programming at the console and inspect
wire connections at the probe. If the problem persists, contact FFS
Technical Services for support.
Product volume error
Tank
The Product Volume as reported
by the probe has exceeded the
limits of the tank.
Check for proper probe and tank programming at the console. If
programming is correct, inspect the probe to ensure that the float is
not stuck in the riser or is otherwise obstructed.
RTD table error
Tank
RTD distance error; Special Probe
programming error.
Verify correct RTD programming. If issue still exists, inspect wiring to
probe.If the condition still exists, contact Franklin Fueling Systems’
Technical Services for support.
System memory error
System
The system has detected a low
memory situation.
Contact FFS Technical Services for support.
Tank Gross Leak Detected
Tank
Tank Gross leak test detected
tank. Suspect possible leak.
Review tank leak test history and programming.
Refer to Section 5: Misc. / Tank Leak Tests – Type and Frequency for
instructions on manually starting line leak tests.
Tank Leak Detected
Tank
Tank leak detected. Suspect
possible leak.
Review tank leak test history and programming.
Refer to Section 5: Misc. / Tank Leak Tests – Type and Frequency for
instructions on manually starting line leak tests.
Tank Product Density
High Limit Exceeded
Tank
The Product Density exceeds the
programmed high limit.
Verify programming if correct this alarm may be an indication of
improper density of the fuel.
Tank Product Density Low
Limit Exceeded
Tank
The Product Density has exceeded
the programmed low limit.
Verify programming if correct this alarm may be an indication of
improper density of the fuel.
Tank SCALD Leak
Detected
Tank
SCALD leak test detected tank
leak. Suspect possible leak.
Review Tank Leak Test History and programming.
Refer to Section 5: Misc. /Tank Leak Tests – Type and Frequency for
more information on SCALD tests.
Tank Delivery Detected
Tank
A delivery has been detected on
the specified tank.
This is not an alarm and should only be a concern if there was not a
delivery to the site at the specified date and time.
Tank Theft Detected
Tank
Product used in Sentinel Mode
exceeds theft limit set. Suspect
theft, and then verify theft limit in
programming.
Verify theft limit in programming. Also obtain an accurate product level
and compare to inventory.
Temperature error
Tank
Special Probe RTD temperature
error detected.
Verify correct RTD table programming. If problem still exists, suspect
wiring or faulty probe.
Ullage error
Tank
Ullage reported has exceeded
tank capacity.
Check for proper probe and tank programming at the console. If
programming is correct, inspect the probe to ensure that the float is not
stuck in the riser or obstructed. Bring the probe inside and wire directly
to the gauge to eliminate possible problems with the field wiring.
Unstable probe
Tank
LL Liquid Level probes can send
FFSsistent data back to console.
Check for proper probe programming at the console and inspect
wire connections at the probe. If the problem persists, contact FFS
Technical Services for support.
Water volume error
Tank
Water volume has exceeded tank
capacity.
Check for proper probe and tank programming at the console. If
programming is correct, inspect the probe to ensure that the colored
water float is on the bottom.