background image

25

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

RS-232

Baud Rate

(9600)

Data transmission speed in bits per second.

1200-57600

Data Bits

(8)

Number of bits that represent data.

7-8

Parity

(None)

Value of parity (error check) bit.

None, Even, Odd

Stop Bits

(1)

Number of stop bits, notifies receiving device of end of

data packet.

1-2

Response Time-out

(8)

Period of time the console will wait for a response from a

remote device.

0-10

Relays

Channel #

Name

(Relay 1)

Given name of the relay.

abc#

Enabled

(Yes)

Whether the Relay is Enabled or not.

Yes/No

Type

(Unknown)

Equipment connected to the relays output.

Unknown

Submersible

Alarm

Solenoid

Dispenser

Other

Polarity

(Normal)

Allows the polarity to be inverted.

Normal, Invert

Logic

(OR Logic)

The type of logic that the gate will use to process incoming

signals. In OR, if any combination of inputs is active, the

relay is active. With AND, when all inputs are active, the

relay is active. In XOR, if all inputs are in the same state

(on / off), the relay is inactive.

OR, AND, XOR

Physically Wired As

(Normally

Open)

How the relay is wired internally.

NO, NC

Number of inputs

(0)

Number of devices that can control the relay.

0-32

Input #

Type

(Unknown

Module)

Chooses which module is inputting the signal to the relay.

Unknown

Controller

Power Supply

IO

AE

4-20

Probe

2-wire Sensor

3-wire Sensor

Low Voltage Inputs

Channel #

Name

(LV Input 1)

Given name of input.

abc#

Enabled

(Yes)

Whether the input is Enabled or not.

Yes/No

Active State

(high)

High will activate channel when high voltage is present.

Low will activate channel with no voltage present.

High / Low

Action

(None)

Create an alarm or event timestamp

None

Alarm

Event

LON

IFSF Node ID

(1)

Allows the T5 Series console to communicate with an

IFSF POS (Point of Sale) System

0-127