beautypg.com

Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual

Page 57

background image

53

Displayed Alarm /

Warning

Device

Description

Recommended Actions

High product volume

Tank

The specified tank has reached

the programmed High Product

Volume.

Check product volume and compare to the programmed High Volume

alarm Limit in the setup menu. Acquire an accurate product level and

compare to the ATG. If levels differ, verify programming is correct. If

alarm persists, contact FFS Technical Services for support.

High High product volume

Tank

The specified tank has reached

the programmed High High

Product Volume.

Check product volume and compare to the programmed High High

Volume alarm Limit in the setup menu. Get an accurate product

volume and compare to the ATG. If levels differ, verify programming is

correct. If alarm persists, contact FFS Technical Services.

High water level

Tank

Water level exceeded High limit

set.

Verify programmed level. If water is too high consult you local site

policy procedures for corrective actions.

Level error

Tank

Product level exceeds tank

diameter due to an error in

console of programming.

Verify tank, offset, and probe programming.

Line monitor disabled

Line

Specified line is not enabled, so

line leak test will not be performed.

Verify line programming. If necessary enable line.

Low battery

Tank

Backup battery is low.

See Installation Guide for replacement instructions.

Low product volume

Tank/Manifold Product volume below Low limit

set. The tank / manifold specified

may be near empty.

Acquire an accurate product volume. If actual product volume in

tank does not match the consoles displayed current volume, verify

programming.

Low low product volume

Tank/Manifold Product volume below Low

Low limit. The tank or manifold

specified may be near empty.

Acquire an accurate product volume, and if does not match the

consoles displayed current volume, verify programming.

Mag installation error

Sensor

The specified TSP-DMS has an

installation error

Check the installation of the TSP-DMS, the sensor must be plumb.

If installation is correct, then try to relearn the sensor. If the problem

persist, the sensor may need to be replaced

Mag product alarm

Sensor

The specified TSP-DMS has

detected product.

Inspect the sump for the presence of product.

Mag sensor configuration

error

Sensor

An error has been detected in the

configuration of the specified TSP-

DMS.

Enter into the setup and inspect the TSP-DMS setup.

Mag sensor data error

Sensor

There is an error with the reported

data from the specified TSP-DMS

Inspect wire connections at the Mag sensor. If the problem persists,

contact FFS Technical Services for support.

Mag sensor float height

error

Sensor

The float height has exceeded the

limits as learned.

Inspect wire connections at the Mag sensor. If the problem persists,

contact FFS Technical Services for support.

Mag sensor float missing

Sensor

The specified TSP-DMS is not

reporting the level information for

one or more float.

Inspect the Mag sensor for damage and redo the connections. If the

Problem persists, contact FFS Technical Services.

Mag sensor missing

Sensor

The console is not receiving any

information from the specified

TSP-DMS.

Inspect wire connections at the Mag sensor. If the problem persists,

contact FFS Technical Services.

Mag sensor not learned

error

Sensor

The specified TSP-DMS was not

properly learned.

Enter into the Control > Mag Sensor screen and have the console

learn the sensor.

Mag sensor

synchronization error

Sensor

The console is receiving

incomplete or improperly timed

data from the specified

TSP-DMS

Inspect wire connections at the Mag sensor. If the problem persists,

contact FFS Technical Services.

Mag water alarm

Sensor

The specified TSP-DMS has

detected water.

Inspect the sump for water.

Mag water warning

Sensor

The TSP-DMS has detected water

above the preset limit.

Inspect the sump for water.

Manifold Delivery

Detected

Tank

A delivery has been detected on

the specified manifold.

This is not an alarm and should only be a concern if there was not a

delivery to the site at the specified date and time.

Manifold Gross Leak

Detected

Tank

A leak in the specified manifolded

tanks has been detected via a

SCALD test. Suspect possible

leak.

Review Tank Leak Test History and programming.

Refer to Section 5: Misc / Tank Leak Tests – Type and Frequency for

instructions on manually starting line leak tests.

Manifold Leak Detected

Tank

A leak in the specified manifolded

tanks has been detected via a

SCALD test. Suspect possible leak

Review Tank Leak Test History and programming.

Refer to Section 5: Misc/Tank Leak Tests – Type and Frequency for

instructions on manually starting line leak tests.

Manifold low product

volume

Tank

The specified manifold has

reached the programmed Low

Product Volume

Check product volume and compare to the programmed Low Volume

alarm Limit in the setup menu. Acquire an accurate product volume

and compare to the ATG. If levels differ, verify programming is correct.

If alarm persists, contact FFS Technical Services for support.