Fms alarms – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 56

52
Displayed Alarm /
Warning
Device
Description
Recommended Actions
VFM No Data
VRM
The Vapor Flow Meter is detected
but is not communicating with the
Console
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Vapor Collection
Failure
VRM
A Weekly Vapor Collection
Warning has occurred for 2
consecutive weeks.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Vapor Collection
Warning
VRM
V / L average for Non-ORVR
transactions is greater than 1.32
or less than 0.81.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Warning
VRM
Ullage pressure is greater than
+1.3” WC for 5% of time.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Failure
VRM
A Weekly Ullage Pressure
Warning has occurred for 2
consecutive weeks.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Leak Test Failure
VRM
The leak rate of the vapor
recovery system is two times the
allowable rate as stated in TP-
201.3 for one week.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Leak Test Warning
VRM
A Weekly Ullage Pressure Leak
Test Warning has occurred for 2
consecutive weeks
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Remote DTU is Offline
DTU
The console cannot detect the
specified DTU.
Wrong ID Number
Dispenser Powered Off
Not installed correctly
Not on same phase voltage as console DTU
DTU FFS Interference
DTU
Two networks have the same
Network ID or nearby FFS
equipment is causing interference
with the system.
Verify Network ID programming in Setup Menu. DTU’s may be in
service at a nearby location that is causing interference. Contact
FFS Technical Services for support
DTU Non FFS
Interference
DTU
Non-FFS equipment is causing
interference with the DTU signals.
Contact FFS Technical Services for support.
FMS Alarms
Alpha volume correction
error
Tank
This error is caused by a
programming mistake in the
Special Products section.
Verify Special Product Alpha volume correction program parameters.
Contact FFS Technical Services Department for assistance.
API volume correction
error
Tank
This error is caused by a
programming mistake in the
Special Products section.
Verify Special Product API volume correction program parameters.
Contact FFS Technical Services Department for assistance.
Correction table error
Tank
Level and Volume mismatch
detected in Correction table
programming.
Verify that all levels and volumes are entered accurately into the
Correction Table programming.
Density float error
Tank
A communication error has
occurred involving the density
float.
Verify programming and contact FFS Technical Services for support.
Density error
Tank
The density of the product is not
within specifications.
Enter setup and verify the information under density in the probe
programming.
Float height error
Tank
This error could indicate that the
wrong float type is installed or that
a programming error has occurred.
Review probe programming for proper float type, number of floats in
the tank. (This would be an idea time to clean the probe and floats).
Float Missing
Tank
Probe detects a lesser number of
floats than programmed.
Review probe programming for correct number of floats. If correct
then inspect probe shaft, floats, and float magnets. With the probes
out of the tank, this would be an idea time to clean the probe and
floats. If pressures meets requirements specified, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
FMS configuration error
None
Conflicts exist within FMS
Application programming.
Verify FMS setting are correct in accordance with the site
specifications.
High product level
Tank
Product level exceeded High limit
set. Possible close to tank overfill
condition
Acquire an accurate product level. If actual product level in tank does
not match the consoles displayed current level, verify programming is
correct.
High high product level
Tank
Product level exceeded High High
limit set. Possible tank overfill
condition.
Acquire an accurate product level. If actual product level in tank does
not match the consoles displayed current level, verify programming is
correct.