Fms alarms – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual

Page 56

background image

52

Displayed Alarm /

Warning

Device

Description

Recommended Actions

VFM No Data

VRM

The Vapor Flow Meter is detected

but is not communicating with the

Console

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Vapor Collection

Failure

VRM

A Weekly Vapor Collection

Warning has occurred for 2

consecutive weeks.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Vapor Collection

Warning

VRM

V / L average for Non-ORVR

transactions is greater than 1.32

or less than 0.81.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Ullage Pressure

Warning

VRM

Ullage pressure is greater than

+1.3” WC for 5% of time.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Ullage Pressure

Failure

VRM

A Weekly Ullage Pressure

Warning has occurred for 2

consecutive weeks.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Ullage Pressure

Leak Test Failure

VRM

The leak rate of the vapor

recovery system is two times the

allowable rate as stated in TP-

201.3 for one week.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Weekly Ullage Pressure

Leak Test Warning

VRM

A Weekly Ullage Pressure Leak

Test Warning has occurred for 2

consecutive weeks

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Remote DTU is Offline

DTU

The console cannot detect the

specified DTU.

Wrong ID Number
Dispenser Powered Off
Not installed correctly
Not on same phase voltage as console DTU

DTU FFS Interference

DTU

Two networks have the same
Network ID or nearby FFS
equipment is causing interference
with the system.

Verify Network ID programming in Setup Menu. DTU’s may be in
service at a nearby location that is causing interference. Contact
FFS Technical Services for support

DTU Non FFS

Interference

DTU

Non-FFS equipment is causing

interference with the DTU signals.

Contact FFS Technical Services for support.

FMS Alarms

Alpha volume correction

error

Tank

This error is caused by a

programming mistake in the

Special Products section.

Verify Special Product Alpha volume correction program parameters.

Contact FFS Technical Services Department for assistance.

API volume correction

error

Tank

This error is caused by a

programming mistake in the

Special Products section.

Verify Special Product API volume correction program parameters.

Contact FFS Technical Services Department for assistance.

Correction table error

Tank

Level and Volume mismatch

detected in Correction table

programming.

Verify that all levels and volumes are entered accurately into the

Correction Table programming.

Density float error

Tank

A communication error has

occurred involving the density

float.

Verify programming and contact FFS Technical Services for support.

Density error

Tank

The density of the product is not

within specifications.

Enter setup and verify the information under density in the probe

programming.

Float height error

Tank

This error could indicate that the

wrong float type is installed or that

a programming error has occurred.

Review probe programming for proper float type, number of floats in

the tank. (This would be an idea time to clean the probe and floats).

Float Missing

Tank

Probe detects a lesser number of

floats than programmed.

Review probe programming for correct number of floats. If correct

then inspect probe shaft, floats, and float magnets. With the probes

out of the tank, this would be an idea time to clean the probe and

floats. If pressures meets requirements specified, contact Franklin

Fueling Systems’ Technical Services Dept. for support on this issue.

FMS configuration error

None

Conflicts exist within FMS

Application programming.

Verify FMS setting are correct in accordance with the site

specifications.

High product level

Tank

Product level exceeded High limit

set. Possible close to tank overfill

condition

Acquire an accurate product level. If actual product level in tank does

not match the consoles displayed current level, verify programming is

correct.

High high product level

Tank

Product level exceeded High High

limit set. Possible tank overfill

condition.

Acquire an accurate product level. If actual product level in tank does

not match the consoles displayed current level, verify programming is

correct.