51

Displayed Alarm /

Warning

Device

Description

Recommended Actions

Relay module number

mismatch

slot

Relay Modules detected does not

match the number programmed.

Check that the number of Relay Modules installed matches the num-

ber programmed under System Configuration > Modules Expected.

Check for a flashing green light or no light at all on the AC Input

Module and contact FFS Technical Services for support.

Relay Module Setup Error

None

An error exists in the Relay

Module configuration

Inspect the Relay Module setup configuration for possible errors. Pay

particular attention to if the module is configured for 10amps or not.

Secondary Containment

Monitor Setup Error

None

An error exists in the configuration

of the Secondary Containment

Monitoring Setup.

Inspect the Secondary Containment Monitor setup configuration for

possible errors.

System bus error

Slot

Data transfer errors occurred in

the System Bus.

Upgrade to the latest version of firmware available at:

www.franklinfueling.com

System Setup Error

None

There is an error in the Setup

configuration.

Inspect the System setup configuration for possible errors.

Vapor Recovery Monitor

Setup Error

None

An error exists in the configuration

of the Vapor Recovery Monitoring

Setup.

Inspect the Vapor Recovery Monitory setup configuration for possible

errors.

VRM Alarms

Daily Vapor Collection

Failure

VRM

A Daily Vapor Collection Warning

has occurred for 2 consecutive

days.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Daily Vapor Collection

Warning

VRM

V / L average for Non-ORVR

transactions is greater than 1.90

or less than 0.33.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

External ATG Connection

Down Error

VRM

The TS-EMS is no longer

communicating to the External ATG.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

External ATG Connection

Down Warning

VRM

An External ATG Connection

Down Error has occurred for 2

consecutive days.

An External ATG Connection Down Error has occurred for 2

consecutive days.

Monthly Ullage Pressure

Warning

VRM

Ullage pressure is greater than

+0.3” WC for 25% of time.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Monthly Ullage Pressure

Failure

VRM

A Monthly Ullage Pressure

Warning has occurred for 2

consecutive months .

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Pressure Out of Range for

Ullage Pressure Leak Test

VRM

Pressure is out of specification to

perform the Ullage Pressure Leak

test.

Verify TSP-VPS for proper calibration. Contact FFS Technical

Services for more information.

Pressure Sensor Open

Circuit

VRM

Communication has been partially

or entire lost.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

TS-DIM Connection Down

VRM

The TS-DIMIB is not receiving

communications from the

dispensers.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Ullage Volume Insufficient

VRM

The Ullage Volume as reported

by either the internal probes or

the external Tank Gauge is not

adequate.

Verify ullage volume and check programming.

Vapor Processor Input

VRM

Processor run time exceeds

62 continuous minutes (as

determined by the Hirt Processor),

or processor is shutoff or input to

ISD console is disconnected

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Vapor Processor Warning

VRM

The ullage pressure exceeds

2.00 inches water column gauge

(WCG) for 144 minutes in one day

(90th percentile > 2.00” WCG as

determined by the VPS sensor).

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

Vapor Processor Failure

VRM

A Vapor Processor Warning alarm

has lasted 48 hours.

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

VFM Error

VRM

The Vapor Flow Meter is only

partially communicating with the

Console

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help.

VFM Missing

VRM

The Vapor Flow Meter is not

detected by the Console

Refer to Vapor Recovery Monitoring Alarm and Troubleshooting

identification guide 000-0529 for troubleshooting help