Vrm alarms – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 55

51
Displayed Alarm /
Warning
Device
Description
Recommended Actions
Relay module number
mismatch
slot
Relay Modules detected does not
match the number programmed.
Check that the number of Relay Modules installed matches the num-
ber programmed under System Configuration > Modules Expected.
Check for a flashing green light or no light at all on the AC Input
Module and contact FFS Technical Services for support.
Relay Module Setup Error
None
An error exists in the Relay
Module configuration
Inspect the Relay Module setup configuration for possible errors. Pay
particular attention to if the module is configured for 10amps or not.
Secondary Containment
Monitor Setup Error
None
An error exists in the configuration
of the Secondary Containment
Monitoring Setup.
Inspect the Secondary Containment Monitor setup configuration for
possible errors.
System bus error
Slot
Data transfer errors occurred in
the System Bus.
Upgrade to the latest version of firmware available at:
www.franklinfueling.com
System Setup Error
None
There is an error in the Setup
configuration.
Inspect the System setup configuration for possible errors.
Vapor Recovery Monitor
Setup Error
None
An error exists in the configuration
of the Vapor Recovery Monitoring
Setup.
Inspect the Vapor Recovery Monitory setup configuration for possible
errors.
VRM Alarms
Daily Vapor Collection
Failure
VRM
A Daily Vapor Collection Warning
has occurred for 2 consecutive
days.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Daily Vapor Collection
Warning
VRM
V / L average for Non-ORVR
transactions is greater than 1.90
or less than 0.33.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
External ATG Connection
Down Error
VRM
The TS-EMS is no longer
communicating to the External ATG.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
External ATG Connection
Down Warning
VRM
An External ATG Connection
Down Error has occurred for 2
consecutive days.
An External ATG Connection Down Error has occurred for 2
consecutive days.
Monthly Ullage Pressure
Warning
VRM
Ullage pressure is greater than
+0.3” WC for 25% of time.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Monthly Ullage Pressure
Failure
VRM
A Monthly Ullage Pressure
Warning has occurred for 2
consecutive months .
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Pressure Out of Range for
Ullage Pressure Leak Test
VRM
Pressure is out of specification to
perform the Ullage Pressure Leak
test.
Verify TSP-VPS for proper calibration. Contact FFS Technical
Services for more information.
Pressure Sensor Open
Circuit
VRM
Communication has been partially
or entire lost.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
TS-DIM Connection Down
VRM
The TS-DIMIB is not receiving
communications from the
dispensers.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Ullage Volume Insufficient
VRM
The Ullage Volume as reported
by either the internal probes or
the external Tank Gauge is not
adequate.
Verify ullage volume and check programming.
Vapor Processor Input
VRM
Processor run time exceeds
62 continuous minutes (as
determined by the Hirt Processor),
or processor is shutoff or input to
ISD console is disconnected
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Vapor Processor Warning
VRM
The ullage pressure exceeds
2.00 inches water column gauge
(WCG) for 144 minutes in one day
(90th percentile > 2.00” WCG as
determined by the VPS sensor).
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
Vapor Processor Failure
VRM
A Vapor Processor Warning alarm
has lasted 48 hours.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
VFM Error
VRM
The Vapor Flow Meter is only
partially communicating with the
Console
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help.
VFM Missing
VRM
The Vapor Flow Meter is not
detected by the Console
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identification guide 000-0529 for troubleshooting help