Power Supply Module
The Power Supply is a non-intrinsically safe module that provides power to the T5 series console from line voltage rated 110 - 240
VAC. This module is two inches wide, occupies two slots and is located immediately to the right of the Controller Module.
The Power Supply Module has two AC / DC switching power supplies: one power supply is +5 V and the other is +24 V.
The Power Supply also has two relay outputs for use with remote annunciators and two low voltage inputs for emergency
generator applications.
Group Name
Parameter Name
Parameter
Default
Description
Parameter
Input
Power Supply
RS-485
Enable Interface
(Yes)
Enables RS-485 options
Yes / No
TS-TPI
Enable Interface
(Yes)
Enables TS-TPI options.
Yes / No
Controllers
Number of Controllers
(0)
The number of controllers being monitored
1-31
Controller # Name
Pump 1
Descriptive name used to identify input
abc#
Enabled
(Yes)
Enables the output
Yes / No
Type
(Unknown)
The type of FE Petro Smart Controller
• Variable
Frequency
• Smart
• Smart 1
• 3 Phase Smart
208/380V
• Mag/Eco
• Unknown
Address
(0)
The slave address of the controller as configured by the
DIP switches on the Smart Controller.
0 - 30
Group
(0)
The Group number this pump is in. Put Pumps located
in similar products into the same group for Leveling or
Priority mode.
0 - 15
Tank
(0)
The tank number (where this Pump is located).
0 - 29
Height
(5.00)
The height of the Pump Motor Assembly off of the bottom
of the tank in inches.
#
Number of inputs
(0)
The number of inputs that will have control over activating
and deactivating this Pump.
0 - 32
Groups
Number of groups
(0)
The number of Groups as assigned under controllers.
0 - 15
Group #
Name
Group 1
Descriptive name used to identify input.
abc#
Mode
(None)
Select the mode you want. (Refer to the TPI section for
more details).
Leveling
Priority
None
Mode: None
Master / Slave
(No)
Select yes if you want both pumps to run during periods of
high demand.
Yes / No
Alternating
(No)
Select yes if you want the pumps to alternate when hook
signals drop out.
Yes / No
Fault Shutdown
(No)
Select yes if you want both pumps to shutdown upon an
alarm.
Yes / No
Mode: Leveling
Master / Slave
(No)
Select yes if you want both pumps to run during periods of
high demand.
Yes / No
Fault shutdown
(No)
Select yes if you want both pumps to shutdown upon an
alarm.
Yes / No
Mode: Priority
Reserve
(20)
The percent of volume that the pump will switch to the
next in the group.
# %
Master / Slave
(No)
Select yes if you want all pumps to run during periods of
high demand.
Yes / No
Fault shutdown
(No)
Select yes if you want all pumps to shutdown upon an
alarm.
Yes / No
Comm 2
Baud rate
(9600)
Data transmission speed in bits per second.
1200-57600
Data Bits
(8)
Number of bits that represent data.
7-8
Parity
(None)
Value of parity (error check) bit.
None, Even, Odd
Stop Bits
(1)
Number of stop bits, notifies receiving device of end of
data packet.
1-2
Response Time-out
(8)
Period of time the device will wait until transmission stops
in seconds.
1-10