List of alarms and troubleshooting, System alarms – Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual

Page 53

background image

49

List of Alarms and Troubleshooting

For all alarms conditions, the troubleshooting steps provided in this chapter are suggested actions to take in the event of

an alarm. Follow all site policy procedures set by local governing agencies in the case of a spill, leak, or malfunction. If

the steps provided by this manual or the site policy are followed and the system still requires additional support, contact

Franklin Fueling Systems Technical Services.
Alarms are listed in sections for System Alarms, VRM Alarms, FMS Alarms, SCM Alarms, Wire Sensor Alarms, LLD

Alarms, TPI Alarms, Printer Alarms and Miscellaneous Alarms.

System Alarms

Displayed Alarm /

Warning

Device

Description

Recommended Actions

2-Wire Sensor Module is

Offline

Slot

2-Wire Sensor Module is offline

due to unknown causes.

Follow safety procedures before working inside of the console.

Visually verify a steady, green “Run” light. If a red “Err” light is flashing

or steady, try to reboot the system. If the condition still exists, contact

Franklin Fueling Systems’ Technical Services Dept. for support on

this issue.

2-Wire Sensor Module

Setup Error

None

Programming errors made during

setup of the 2-Wire Sensor

Module.

Verify 2-Wire Sensor Module programming parameters. If the

condition still exists, contact Franklin Fueling Systems’ Technical

Services Dept. for support on this issue.

2-Wire Sensor module

number mismatch

Slot

2-Wire Sensor Modules detected

does not match the number

programmed.

At startup check that the number of 2-Wire Sensor Modules installed

matches the number programmed under System Configuration >

Modules Expected. On machines that are in service: Check for a

flashing green light or no light at all on the 2-Wire Sensor Module and

contact FFS Technical Services for support.

3-Wire Sensor Module is

Offline

Slot

3-Wire Sensor Module is offline

due to unknown causes.

Follow safety procedures before working inside of the console.

Visually verify a steady, green “Run” light. If a red “Err” light is flashing

or steady, try to reboot the system. If the condition still exists, contact

Franklin Fueling Systems’ Technical Services Dept. for support on

this issue.

3-Wire Sensor Module

Setup Error

None

Programming errors made during

setup of the 3-Wire Sensor

Module.

Verify 3-Wire Sensor Module programming parameters. If the

condition still exists, contact Franklin Fueling Systems’ Technical

Services Dept. for support on this issue.

3-Wire Sensor Module

Mismatch

Slot

3-Wire Sensor Modules detected

does not match the number

programmed.

At startup check that the number of 3-Wire Sensor Modules installed

matches the number programmed under System Configuration >

Modules Expected. On machines that are in service: Check for a

flashing green light or no light at all on the 3-Wire Sensor Module and

contact FFS Technical Services for support.

4-20mA Module is Offline

Slot

4-20mA Module is offline due to

unknown causes.

Follow safety procedures before working inside the console. Visually

verify a steady green “Run” light. If a red “Err” light is flashing or

steady, try to reboot system. If the condition still exists, contact

Franklin Fueling Systems’ Technical Services Dept. for support on

this issue.

4-20mA Module Number

Mismatch

Slot

4-20 mA Modules detected

does not match the number

programmed.

Check that the number of 4-20mA Modules installed matches

the number programmed under System Configuration > Modules

Expected. Check for a flashing green light or no light at all on the

4-20mA Module and contact FFS Technical Services for support

4-20mA Module Setup

Error

None

Programming errors made during

setup of the 4-20mA Module.

Verify 4-20mA Module programming. If the condition still exists,

contact Franklin Fueling Systems’ Technical Services Dept.

4-20mA Input Error

ChannelANA

Errors have been detected in the

an analog input channel

If the input is not being used, set the programming to reflect proper

input type. If the input is being used as an analog signal, inspect the

wiring and redo connections.

AC Input Module is Offline

Slot

AC Input Module is offline due to

unknown causes.

Follow safety procedures before working inside of the console.

Visually verify a steady green “Run” light. If a red “Err” light is flashing

or steady, try to reboot system. If the condition still exists, contact

Franklin Fueling Systems’ Technical Services Dept. for support on

this issue.

AC Input module number

mismatch

Slot

AC Input Modules detected

does not match the number

programmed.

Check that the number of AC Input Modules installed matches

the number programmed under System Configuration > Modules

Expected. Check for a flashing green light or no light at all on the AC

Input Module and contact FFS Technical Services for support.

AC Input Module Setup

Error

None

Programming errors made during

setup of the AC Input Module.

Verify AC Input Module programming parameters. If the condition still

exists, contact Franklin Fueling Systems’ Technical Services Dept. for

support on this issue.

AC Input Alarm

None

An input on the AC input module

has been configured as an

alarm and is active.

Check the programming and voltage inputs for the specified Input

channel on the AC Input module.