Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual

Page 54

background image

50

Displayed Alarm /

Warning

Device

Description

Recommended Actions

Console DTU is offline

Slot

The Console DTU is not

communicating with the Console

Check for proper wire connection between the console and the

Console DTU. Verify DTU input power. Replace DTU

Console DTU number

mismatch

Slot

The number of DTU Modules

detected does not match the

number programmed.

Ensure that a console DTU is being used. Possible bad bus
connection. Not powered. Replace DTU if connections and settings
check good.

Controller Module is

Offline

Slot

Controller Module is offline due to

unknown causes.

Follow safety procedures before working inside the console. Visually

verify a steady green “Run” light. If red “Err” light is flashing or steady

try to reboot system. If the condition still exists, contact Franklin

Fueling Systems’ Technical Services Dept. for support on this issue.

DIM module number

mismatch

Slot

DIM modules detected does not

match the number programmed.

Check that the number of DIM Modules installed matches the number

programmed under System Configuration > Modules Expected. If

problem persists, contact FFS Technical Services for support

Internal Error #1

System

There is an internal buffer error

occurring in the gauge.

Contact FFS Technical Services for support

Invalid Configuration

None

The configuration that has been

loaded is not valid.

Verify the file type of the configuration which is being uploaded

Invalid Registration

None

The registration that is loaded is

not valid.

If you have upgraded the site before, use the upgrade tool to restore

the former registration. If you have not upgraded the site before,

contact FFS Technical Services for support.

IO Input Alarm

None

An input on the Input/Output

module has been configured as an

alarm and is active.

Check the programming and voltage inputs for the specified Input

channel on the IO module.

IO Module is offline

Slot

The IO Module is not

communicating with the Console

Inspect the IO module for error lights. If green light is flashing,

recover the module. If the lights are off: Power down, remove / re-

seat the module and power back up. If problem persists, contact FFS

Technical Services for support

IO module number

mismatch

Slot

IO Modules detected does not

match the number programmed.

Check that the number of IO Modules installed matches the num-

ber programmed under System Configuration > Modules Expected.

Check for a flashing green light or no light at all on the IO Module and

contact FFS Technical Services for support.

IS Barrier Violation

None

Non-Intrinsically Safe module

placed in IS area; or IS Barrier is

removed.

Check the module configuration to ensure that a module has not

been improperly placed. Power down and then remove / re-seat the IS

barrier. If problem persists contact FFS Technical Services for support

LON module number

mismatch

Slot

Lon Modules detected does not

match the number of Lon Modules

programmed.

Check that the number of LON Modules installed matches the num-

ber programmed under System Configuration > Modules Expected.

If problem persists, contact FFS Technical Services for support.

Power Supply Input Alarm

None

An input on the Power Supply has

been configured as an alarm and

is active.

Check the programming and voltage inputs for the specified Low

Voltage Input channel on the Power Supply module.

Power Supply Module

number mismatch

Slot

Power Supply Modules detected

does not match the number

programmed.

Check that the number of Power Supply Modules installed matches

the number programmed under System Configuration > Modules Ex-

pected. Check for a flashing green light or no light at all on the Power

Supply Module and contact FFS Technical Services for support

Power Supply Module is

Offline

Slot

Power Supply Module is offline

due to unknown causes.

Follow safety procedures before working inside the console. Visually

verify a steady green “Run” light. If red “Err” light is flashing or steady

try to reboot system. If the condition still exists, contact Franklin

Fueling Systems’ Technical Services Dept. for support on this issue.

Power Supply Module

Setup Error

None

Errors in the setup of the listed

module.

The console may need to be reprogrammed.

Printer Module Number

Mismatch

Slot

Printer Modules detected does not

match the number programmed.

Check that the number of Printer Modules installed matches the

number programmed under System Configuration > Modules

Expected. If problem persists, contact FFS Technical Support.

Probe Module is Offline

Slot

Probe Module is not

communicating with the console.

Follow safety procedures before working inside the console. Visually

verify a steady green “Run” light. If red “Err” light is flashing or steady,

re-seat module and reboot system. If the condition still exists, contact

Franklin Fueling Systems’ Technical Support for help on this issue.

Probe Module Number

Mismatch

Slot

Probe Modules detected does

not match the number of Probe

Modules programmed.

Check that the number of Probe Modules installed matches the num-

ber programmed under System Configuration > Modules Expected.

Check for a flashing green light or no light at all on the Probe Module

and contact FFS Technical Services for support.

Probe Module Setup Error

None

Programming errors made during

setup of the Probe Module.

Verify Probe Module programming parameters. If the condition still

exists, contact Franklin Fueling Systems’ Technical Support for help

on this issue.

Relay Module is Offline

Slot

Relay Module is offline due to

unknown causes.

Follow safety procedures before working inside the console. Visually

verify a steady green “Run” light. If red “Err” light is flashing or steady

try to reboot system. If the condition still exists, contact Franklin

Fueling Systems’ Technical Support for help on this issue.