Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 52

48
TPI Setup
Group Name
Parameter Name
Parameter
Default
Description
Max Value
Power Supply
RS-485
TS-TPI
Enable Interface
(Yes)
Enables TS-TPI options.
Yes/No
Controllers A* Number of Controllers
(2)
Number of controllers to be connected
31
Controller 1 Name
Unlead Pump 1
Given Name of the pump controller
abc#
Enabled
(Yes)
Enables the controller.
Yes / No
Type
(Mag/ECO)
Type of controller used
Variable Frequency
Smart
3 phase smart
Smart I
Mag / Eco
unknown
Address
(1)
Unique address of the controller
30
Group
(0)
Controller group number (if a member of a group)
15
Tank
(1)
Tank associated with controller
48
Height
(5.00 in)
Approximate distance of pump motor from tank
bottom
#
Number of Inputs
(1)
Number of inputs that will activate controller
32
Input 1 Type
AC Input Module
Select module that contains the input
Modules listed
Channel
Disp. 1/2 Unleaded Specific input that will activate the controller
12
Controller 2 Name
Unlead Pump 2
Given Name of the pump controller
abc#
Enabled
(Yes)
Enables the controller.
Yes / No
Type
(Mag/ECO)
Type of controller used
Variable Frequency
Smart
3 phase smart
Smart I
Mag / Eco
unknown
Address
(1)
Unique address of the controller
30
Group
(0)
Controller group number (if a member of a group)
15
Tank
(1)
Tank associated with controller
48
Height
(5.00 in)
Approximate distance of pump motor from tank
bottom
#
Number of Inputs
(1)
Number of inputs that will activate controller
32
Input 1 Type
AC Input Module
Select module that contains the input
Modules listed
Channel
Disp. 1/2 Unleaded Specific input that will activate the controller
12
* When in the Edit mode of Setup, an A will appear for AutoConfigure. When the AutoConfigure Option is used, the tank
gauge will locate all of the controllers that are properly wired in the system and identify them.
Note: All DIP switch settings for the FE Petro controllers should be set as stand alone controllers, with the exception of
the addressing. All controllers need to have a unique address that is NOT set to 0).